Outputs - Datalogic MATRIX 450 Reference Manual

Hide thumbs Also See for MATRIX 450:
Table of Contents

Advertisement

4

4.6 OUTPUTS

Two optocoupled general purpose outputs are available. The meaning of the two outputs
Output 1 and Output 2 can be defined by the user. They are typically used either to signal the
data collection result or to control an external lighting system.
CBX100/500
+V
O1+
O1-
O2+
O2-
-V
The electrical features of the two outputs are the following:
V
= 30 Vdc max.
CE
I
= 40 mA continuous max.; 130 mA pulsed max.
CE
V
CE saturation
P
= 80 mW Max. @ 45 °C ambient temp.
D
By default, Output 1 is associated with the Partial Read and No Read events, which activates
when the code(s) signaled by the external trigger are not decoded, and Output 2 is
associated with the Complete Read event, which activates when all the selected codes are
correctly decoded.
The output signals are fully programmable being determined by the configured
Activation/Deactivation events, Deactivation Timeout or a combination of the two. Refer to
the Digital I/O folder in the VisiSet™ Help On Line for further details.
66
Figure 46 - NPN Input 2 Using External Power
Function
Power Source - Outputs
Output 1 +
Output 1 -
Output 2 +
Output 2 -
Power Reference Outputs
= 1 Vdc max. @ 10 mA
MATRIX 450™ REFERENCE MANUAL
Input Device
Pulled up to External
Input Device Power
Input
Signal