J3-00 - Outdoor Unit: Malfunction Of Discharge Pipe Thermistor/Compressor Body Thermistor; J5-00 - Malfunction Of Suction Pipe Thermistor - Daikin Sky Air Advance RZA200D7Y1B Service Manual

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

2
|
Troubleshooting
2.4.13 J3-00 – Outdoor unit: Malfunction of discharge pipe thermistor/compressor body
thermistor
2.4.14 J5-00 – Malfunction of suction pipe thermistor
Service manual
28
Trigger
Discharge pipe thermistor
or compressor body
thermistor input is out of
range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform
a
check
"3.15 Thermistors" [
Possible cause: Faulty discharge pipe thermistor or connector fault.
2 Perform
a
check
"3.15 Thermistors" [
Possible cause: Faulty compressor body thermistor or connector fault.
3 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Suction pipe thermistor
input is out of range
range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform
a
check
"3.15 Thermistors" [
Possible cause: Faulty suction pipe thermistor or connector fault.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Effect
Unit will stop operating.
of
the
discharge
4
 128].
of
the
compressor
4
 128].
"3.9 Main
Effect
Unit will stop operating.
of
the
suction
4
 128].
"3.9 Main
Reset
Manual reset via user
interface.
pipe
thermistor.
body
thermistor.
4
PCB" [
 95].
Reset
Automatic reset.
pipe
thermistor.
4
PCB" [
 95].
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
See
See