J3" Outdoor Unit: Malfunction Of Discharge Pipe Thermistor (R2T) - Daikin VRV III-S RXYMQ6PV4A Service Manual

For high outdoor temperature use, r-410a
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
3.23 "J3 " Outdoor Unit:
Thermistor (R2T)
J3
Remote
Controller
Display
Applicable
RXYMQ6P
Models
Method of
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Detection
Malfunction
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
156
Malfunction of Discharge Pipe
Defect of thermistor (R2T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to
outdoor unit
PC board
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R2T from the outdoor
unit PC board.
(5.0kΩ~
640kΩ)
YES
Refer to thermistor resistance / temperature characteristics table on P229.
NO
NO
SiME34-608
Connect the thermistor and turn
on again.
Replace the thermistor (R2T).
Replace outdoor unit PC board
(A1P).