To replace the clogged/leaking part of the refrigerant circuit
To recuperate the refrigerant
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
a
Liquid stop valve
b
Gas stop valve
2 Completely open the stop valves by screwing the stop valve screw
counterclockwise.
Is the problem solved?
Yes
No
1 See the correct procedure for the component that needs to be repaired. See
also
"Repair
information" [
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
1 Necessary tools:
Service tool
a
b
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4
 146] for more details.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Refrigerant recovery unit
4
Third party components
|
Remark
Compatible with the
refrigerant to be
recovered
Service manual
143