Via The Outdoor Unit - Daikin Sky Air Advance RZA200D7Y1B Service Manual

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

2.2.3 Via the outdoor unit

RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
#
Action
1
Tap the settings icon.
2
Tap Errors and
warnings.
3
Tap Error history.
Error code descriptions are accessible on "Mode 1: Monitor Mode".
The table below shows which setting shows the error codes that led to an outdoor
unit forced stop.
When an error is generated, the unit performs a forced off until the error is
retrieved. The current error code will be shown on the 7‑segment display. You can
also access the error history on "Mode 1: Monitor Mode".
Image for reference
2
Troubleshooting
|
Result
The Unit settings
screen is displayed.
The Errors and
warnings screen is
displayed.
The Error history screen
is displayed.
Service manual
11