3.10 Noise filter PCB

3.10.1 Checking procedures

To perform a power check of the noise filter PCB
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
b
a
c
a
Fuse F1U
b
Fuse F2U
c
Fuse F3U
Is the problem solved?
Yes
No
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Access the back side of the switch box, see
2 Turn ON the power of the unit.
3 Measure the voltage between the phases L1A‑L2A‑L3A on the noise filter PCB.
Result: All measurements MUST be 400 V AC ± 10%.
4 Measure the voltage between each phase and N on the noise filter PCB.
Result: The measured voltages MUST be 230 V AC ± 10%.
3
Action
No further actions required.
Return to
"3.9.1 Checking
4
procedures" [
 95] of the PCB and
continue with the next procedure.
"3.12 Plate
work" [
"3.12 Plate
work" [
Components
|
4
 111].
4
 111].