Daikin Sky Air Advance RZA200D7Y1B Service Manual page 104

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

3
|
Components
To check the fuses of the noise filter PCB
Service manual
104
1 Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2 Check that no connectors or wires are damaged.
3 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 151].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier checks of the noise filter PCB, see
"3.10.1 Checking
procedures" [
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
b
a
Fuse F101U
b
Fuse F102U
Blown fuse on the noise filter PCB?
Yes
No
Action
No further actions required.
Return to
"3.10.1 Checking
procedures" [
PCB and continue with the next
procedure.
4
 101].
a
Action
Replace the noise filter PCB, see
"3.10.2 Repair
Return to
"3.10.1 Checking
procedures" [
PCB and continue with the next
procedure.
"6.2  Wiring
4
 101] of the noise filter
4
procedures" [
 105].
4
 101] of the noise filter
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05