Daikin Sky Air Advance RZA200D7Y1B Service Manual page 57

Hide thumbs Also See for Sky Air Advance RZA200D7Y1B:
Table of Contents

Advertisement

To perform a mechanical check of the compressor
To perform an electrical check of the compressor
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Prerequisite: First perform an auditive check of the compressor, see
"3.2.1 Checking
procedures" [
Prerequisite: Stop the unit operation via the user interface.
1 Turn OFF the respective circuit breaker.
2 Check the compressor dampers and piping for any damage.
a
1
Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers and piping are in
a good condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 56].
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
rectifier
voltage" [
2 Remove the cover of the compressor wire terminals.
4
 56].
a
Action
Perform an electrical check of the
compressor, see
procedures" [
Replace the compressor, see
"3.2.2 Repair
4
 135].
3
Components
|
"3.2.1 Checking
4
 56].
4
procedures" [
 61].
"3.2.1  Checking
"To check the
Service manual
57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sky air advance rza250d7y1b

Table of Contents