Overview of field settings for indoor units
The overview lists the field settings for the indoor unit FCAG-B. For more detailed field settings and field settings of
other indoor units, see service manual of the indoor units. Bold content is default setting.
st
Mode
1
code
10(20)
0
1
2
3
(3)
7
(4)
8
11(21)
2
3
4
(5)
6
RZA200+250D7Y1B
Sky Air Advance-series
ESIE19-13A – 2020.05
Description function
Filter cleaning sign interval / Long
life filter
Filter type
Remote controller thermistor
Filter cleaning sign
Detection time for NOT presence
Compensation of suction air
temperature in heating mode
Fan OFF at thermostat OFF
Airflow rate setting during
heating
Automatic operation mode
control
Sensitivity of presence sensor
nd
2
code
Description selection
01
2500 hr
02
1250 hr
01
Long
02
Super long
01
Enabled
02
Disabled
01
Display
02
No display
01
30 minutes
02
60 minutes
01
COMPENSATE
Temperature [A+2]°C which an air
conditioner controls when the
temperature of a remote
controller is A°C)
02
NO COMPENSATION
Temperature [A]°C which an air
conditioner controls when the
temperature of a remote
controller is A°C)
01
Normal
02
OFF
01
Standard
02
Slight up
03
Up
01
Available
02
Prohibition
01
High
02
Low
03
Standard
04
Sensor does not work
6
Technical data
|