External boiler controller OPEN/CLOSED or STAGE2 / STAGE3 (X5-03
pin 2 / X5-03 pin 3)
This input serves for the connection of an external controller with contact outputs. The
input is only active when configured as External load controller.
Parameter
LC_OptgMode (ExtLC X5-03)
2 operating modes are possible. The operating mode that is active depends on the
parameterization of the fuel-air ratio control system.
Multistage operation can be implemented by using additional thermostats / pressure
switches.
Parameter
Operation Mode (2-stage / 3-stage)
X5-03 pin 3
X5-03 pin 2
(OPEN)
(CLOSED)
0
0
0
1
1
0
1
1
X5-03 pin 3
X5-03 pin 2
(OPEN)
(CLOSED)
0
0
0
1
1
0
1
1
X5-03 pin 3
X5-03 pin 2
(OPEN)
(CLOSED)
0
0
0
1
1
0
1
1
Parameter
Config X5-03 (LMV5x std / LMV2/3 std / LMV2/3 inv)
The burner's output can be increased or decreased by means of a 3-position step
controller output with 2 relays.
«▲» increases the output
«▼» decreases the output
If none of the 2 inputs is active, the burner's output is maintained at a constant level.
The shortest permissible positioning step is about 100 ms.
Parameter
Operation Mode (modulating)
Basic Documentation LMV5...
4 Burner control
3-stage
2-stage
Stage 1
Stage 1
Stage 1
Stage 1
Stage 2
Stage 2
Stage 3
Stage 2
3-stage
2-stage
Stage 1
Stage 1
Stage 3
Stage 2
Stage 2
Stage 2
Stage 3
Stage 2
3-stage
2-stage
Stage 1
Stage 1
Stage 2
Stage 1
Stage 3
Stage 2
Stage 3
Stage 2
47/327