15.3 Cross-sectional areas

The cross-sectional areas of the mains supply lines (L, N, PE) and – if applicable – the
safety loop (safety limit thermostat, shortage of water, etc.) must be sized for rated
currents in agreement with the selected external primary fuse.
The cross-sectional areas of the other cables must be sized in agreement with the
internal unit fuse (max. 6.3 AT).
Min. cross-sectional area
Cable insulation must satisfy the requirements of the relevant temperature and
environmental conditions. The CAN (bus) cables have been specified by Siemens and
can be ordered as accessory items. Other types of cables must not be used.
Otherwise, the EMC characteristics of the LMV5 will become unpredictable!
Main voltage
Fuses in the LMV5
- F1
- F2
- F3

15.4 AZL5 display and operating unit

Operating voltage
Power consumption
Degree of protection of housing
- Rear
- Front
Safety class
Battery:
Manufacturer
VARTA
DURACELL
SANYO ELECTRIC, Osaka / Japan
RENATA AG, Itingen / CH
Pollution degree
Basic Documentation LMV5...
15 Technical data
0.75 mm²
(single- or multi-core to VDE 0100)
AC 120 V
AC 230 V
-15% / +10%
-15% / +10%
6.3 AT
6.3 AT
DIN EN 60127 2/5
DIN EN 60127 2/5
4 AT
4 AT
GMD-4A
DIN EN 60127 2/5
4 AT
4 AT
GMD-4A
DIN EN 60127 2/5
AC 24 V -15% / +10%
<5 W (typically)
IP00 to IEC 529
IP54 to IEC 529 (when built in)
I with parts according to II and III as per
DIN EN 60730-1
Type
CR 2430 (LF-1/2 W)
DL 2430
CR 2430 (LF-1/2 W)
CR 2430
2
CC1P7550en
22.05.2018