Advertisement

4. Setting gas valve proving
Menu level 1
Params & Display
5. Addressing the
actuators
Menu level 1
Params & Display
Building Technologies
Menu level 2
Menu level 3
BurnerControl
ValveProving
Selection of gas valve proving: No VP, VP startup, VP shutdown or VP stup/shd
(↑ Gas valve proving system)
Prior to programming the actuators, the connector for the bus connection at the last
CAN bus element must be plugged in.
Menu level 2
Menu level 3
Actuators
Addressing
For addressing an actuator, select the respective type of actuator:
1. Air actuator
2. Gas actuator [for dual-fuel burners with only 1 fuel actuator]
3. Oil actuator
4. Auxiliary actuator
5. Auxiliary actuator 2
6. Auxiliary actuator 3
Confirm by pressing Enter (↑ AZL5).
The AZL5 prompts you to operate the addressing switch on the actuator.
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
Menu level 5
ValveProvingType
Menu level 4
Menu level 5
1 AirActuator
2 GasActuat(Oil)
3 OilActuator
4 AuxActuator
5 AuxActuator2
6 AuxActuator3
Menu level 6
Menu level 6
167/327
CC1P7550en
22.05.2018