Description of connection terminals (cont'd)
Connection symbol
PIN 1
X5-01
PIN 2
PIN 3
PIN 1
X5-02
PIN 2
PIN 3
PIN 1
PIN 2
X5-03
PIN 3
PIN 4
PIN 1
PIN 2
X6-01
PIN 3
PIN 4
PIN 1
PIN 2
X6-02
PIN 3
PIN 1
PIN 2
X6-03
PIN 3
Building Technologies
Description of connections
Protective earth (PE)
˜
I
˜
Pressure switch min-oil (Pmin-oil)
Power signal for pressure switch-
˜
min-oil (Pmin-oil)
˜
Protective earth (PE)
I
Pressure switch-max-oil (Pmax-oil)
˜
Power signal for pressure switch-
˜
max-oil (Pmax-oil)
Controller (ON / OFF)
˜
˜
Controller closes / stage 3
I
Controller opens / stage 2
˜
Power signal for control of controller
˜
˜
˜
I
˜
˜
˜
I
˜
˜
˜
I
˜
Basic Documentation LMV5...
12 Description of connection terminals (AC 230 V)
Start release oil (START)
Power signal start release oil
(START)
Direct heavy oil start
Power signal direct heavy oil start
Protective earth (PE)
Neutral conductor (N)
Oil pump / magnetic coupling
Protective earth (PE)
Neutral conductor (N)
Fuel valve (shut-off valve-oil)
Electrical rating
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 1.5 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
AC 230 V +10 % / -15 %, 50...60 Hz,
2 A, cosι 0.4
AC 230 V +10 % / -15 %, 50...60 Hz,
1 A, cosι 0.4