Precontrol; Calculation Of Precontrol - Siemens LMV50 Series Manual

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

254/327
Building Technologies

19.3 Precontrol

As a result of the measurements made when setting the O2 setpoint, the properties
and the behavior of the burner are learned.
Based on the type of fuel, the O2 ratio value, the O2 setpoint, and the standardized
value, precontrol calculates the air rate reduction such that changes in burner load
do not require the O2 trim controller to interfere.
Calculation of the air rate from the manipulated variable is made such that a manipulated
variable of +10% will offset an air density change of -10%.
To enable precontrol to function correctly, the outputs for the curvepoints must be
parameterized so that they concord with the actual burner output.
Example: 2'000 kW burner:
100% point: 2'000 kW ≈ 200 m³/h natural gas
75% point: 1'500 kW ≈ 150 m³/h natural gas
50% point: 1'000 kW ≈ 100 m³/h natural gas
This can be achieved, for example, by measuring the amount of fuel with a fuel meter
when making the setting.

19.3.1 Calculation of precontrol

Based on the settings for O2 trim control, the system becomes familiar with the
characteristics and behavior of the burner. The lambda factor, which is taken into
consideration when calculating the air rate reduction, reflects these learned behavior.
Precontrol can be calculated in 3 different ways:
like P air
The learned lambda factor is also considered when air density
(temperature / pressure) changes. Air pressure and air density have
an impact on the fuel throughput
like theory
The learned lambda factor is not considered when air density
(temperature / pressure) changes. Air pressure and air density have
no impact on the fuel throughput.
LambdaFact1
The system anticipates a lambda factor of 1. The learned value is
irrelevant.
This parameter setting is only intended for use with burners that have
a lambda factor of 1.
Recommendation:
When firing on gas: like P air
When firing on oil: like theory
For burners where the air pressure does not have any impact on the gas pressure (e.g.
burner head with metal mesh for Super-Low-NOx applications) : LambdaFact1
Parameter
Type Air Change (like P air, like theory LambdaFact1)
Basic Documentation LMV5...
19 O2 trim control with LMV52 and PLL52
CC1P7550en
22.05.2018