Loads On Terminals, Cable Lengths And Cross-Sectional Areas - Siemens LMV50 Series Manual

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

Loads on input terminals
230/327
Building Technologies
15.2 Loads on terminals, cable lengths and cross-
sectional areas
General data
Mains voltage
Perm. mains primary fuse (external)
Unit fuse F1 (internal)
Mains supply: The mains input current depends on the status of the unit
Under voltage
Safety shutdown from operating
position at mains voltage
Restart on increase of mains
voltage
Oil pump / magnetic clutch
(rated voltage)
Rated current
Power factor
Pressure switch relief valve
(rated voltage)
Rated current
Power factor
Status inputs (CFN): Status inputs (with the exception of the safety loop) of the contact
feedback network (CFN) are used for system supervision and require a mains-related
input voltage
Input safety loop
Input currents and input voltages
- UeMax
- UeMin
- IeMax
- IeMin
Recommended contact material for
external signal sources (air pressure
switch, pressure switch-min,
pressure switch max, etc.)
Transition / transient behavior /
bouncing
- Perm. bounce time of contacts
when switching on/off
UN
Voltage detection
- ON
- OFF
Basic Documentation LMV5...
15 Technical data
AC 120 V
-15% / +10%
Max. 16 AT
6,3 AT to
DIN EN 60127 2/5
< AC 96 V
> AC 100 V
1.6 A
Cosι >0.4
0.5 A
Cosι >0.4
Refer to Loads on output terminals
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
Gold-plated silver contacts
Max. 50 ms
(after the bounce time, the contact must be
permanently closed or open)
AC 120 V
AC 90...132 V
< AC 40 V
AC 230 V
-15% / +10%
Max. 16 AT
6,3 AT to
DIN EN 60127 2/5
< AC 186 V
> AC 188 V
2 A
Cosι >0.4
0.5 A
Cosι >0.4
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
AC 230 V
AC 180...253 V
< AC 80 V
CC1P7550en
22.05.2018