94/327
Building Technologies
Pos. [°]
2
+ Value Pos. tolerance
Required position
- Value Pos. tolerance
-2
0
Figure 41: Successful correction <2°
The required position is considered to be reached when it is within ° value Tolerancia
pos. (neutral band).
When reaching a new position within ° value Tolerancia pos. (neutral band), the
electronic ratio control makes a fine adjustment on the actuators.
Corrections are only made to the position if the current position deviates from the
required position by more than the value Tolerancia pos. (neutral band). These
corrections are then followed by another fine adjustment.
If, during the load change, an actuator is mechanically blocked, the supply of fuel is
shut down within 3 or 8 seconds.
Pos. [°]
+ Value Pos. tolerance
Required position
- Value Pos. tolerance
-2
Actual
position
7550d18e/1115
Figure 42: Locking on change of load (approaching <2° / > value position tolerance)
Parameter
Pos. tolerance
It may be necessary to adjust the parameter Pos. tolerance in the event of changing
loads (e.g. fluttering damper).
This parameter can be used to set the tolerated deviation between the actual position
and the target position / target speed specified by the electronic fuel / air ratio control
system.
This means that the previous neutral zone of 0.3° (factory setting) can be increased to
1.2°.
The tolerated deviation of the variable speed drive speed is only increased along with it
from 0.6%. This means that the smallest tolerance value is 0.5% and can be increased
to 1.2% (see following table).
Basic Documentation LMV5...
6 Fuel-air ratio control (FARC)
+ Value Pos. tolerance
Required position
- Value Pos. tolerance
t
< 5 s
Fault < 2° (Stall point at constant output)
< 5 s
Pos. [°]
2
-2
0
< 5 s
Alarm
CC1P7550en
22.05.2018
Alarm
t
t