1.8 Service notes

If fuses are blown, the complete unit must be returned to Siemens.
Notes!
Only authorized persons may replace the fuse (in accordance with EN 298-1, chapter
9.2.r).

1.9 Life cycle

The LMV5 burner control has a designed lifetime* of 250,000 burner startup cycles
which, under normal operating conditions in heating mode, correspond to approx. 10
years of usage (starting from the production date given on the type field).
This is based on the continuous tests specified in standards EN 230/EN 298.
A summary of the conditions has been published by the European Control
Manufacturers Association (afecor - www.afecor.org).
The designed lifetime is based on use of the burner control according to the
manufacturer's Data Sheet and Basic Documentation. After reaching the designed
lifetime in terms of the number of burner startup cycles, or the respective time of usage,
the burner control is to be replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Note!
The total startup counter counts up with each burner startup cycle.
This also occurs if the start attempt is aborted.
For details, refer to chapter on End of life cycle function.

1.10 Disposal notes

The unit contains electrical and electronic components and must not be disposed of
together with domestic waste. Legal and currently valid legislation must be observed.
Basic Documentation LMV5...
1 Safety notes
19/327
CC1P7550en
22.05.2018