Adaption sequence
Β
112/327
Building Technologies
Manual operation,
shutdown or standby
Change to automatic operation
Burner OFF
Setting phase of controlled system, fixed at 5 min
Evaluation of development of actual value. If actual value changes excessively,
setting phase will be extended by another 5 min max
Startup
Saving the startup values and output of the parameterized adaption load
When the temperature or pressure increase changes to a straight line, the delay time Tu
and the maximum increase of the controlled system is ascertained from the measured
values and the start values. These values are then used to calculate the control parameters.
If the adaption load is below 100 %, a correction factor will be used.
Adaption will be terminated or stopped:
- before the setpoint is reached
- in the case of unusual developments of the actual value (e.g. pure dead time member
with extensive dead time)
End of adaption is communicated to the AZL... . If adaption was correct, the control parameters
will be saved in EEPROM. Otherwise, the former control parameters are reinstaled and the
If adaption was successful, the former control parameters in EEPROM will be overwritten.
Note:
The control then uses the new parameters without waiting for an extra confirmation by the
user. The new control parameters appear on the AZL... and are valid from now on.
Figure 55: Modulating control – adaption sequence
Note!
Refer to chapter Displays and settings / special function adaption load controller
Basic Documentation LMV5...
7 Boiler controller / load controller
Manual operation,
Automatic operation,
startup or operation
shutdown or standby
Burner ON, low-fire
Waiting until actual value < setpoint minus 5 %
change to modulating control will take place.
Automatic operation,
startup or operation
Burner OFF
Burner ON, low-fire
Startup
7550f21E/0 502