15 Technical data

15.1 LMV5 and AZL5

Mains voltage
Β
Note!
Only for use in earthed networks!
Transformer AGG5.210 / AGG5.220
- Primary side
- Secondary side 1
- Secondary side 2
Mains frequency
Power consumption
Safety class
Degree of protection of housing
Mode of operation
Rated impulse voltage
Mains voltage and power supply for EMC
emitted interference tests
Basic Documentation LMV5...
15 Technical data
AC 120 V
AC 230 V
-15% / +10%
-15% / +10%
AC 120 V
AC 230 V
AC 12 V
AC 12 V
2 x AC 12 V
2 x AC 12 V
50 / 60 Hz ±6%
50 / 60 Hz ±6%
<30 W (typically)
<30 W (typically)
I with parts according to II and III as per
DIN EN 60730-1
IP00 in accordance with DIN EN 60529
IP40 in accordance with DIN EN 60529
must be ensured through adequate
installation of the LMV5 by the burner or
boiler manufacturer
Type 2B in accordance with DIN EN
60730-1
Rated impulse voltage in accordance with
DIN EN 60730-1; chapter 20 (overvoltage
class III)
The emitted interference measurement is
tested with mains voltage and maximum
power consumption
CC1P7550en
22.05.2018