Pe Cable; Ac Auxiliary Power Cables - ABB Terra HP Generation 3 Installation Manual

Ul 175 kw static dc system
Hide thumbs Also See for Terra HP Generation 3:
Table of Contents

Advertisement

Technical data
Parameter
Minimum test voltage
Ambient temperature range
Maximum cable temperature (on the sur-
face)
Bending radius
12.19.3

PE cable

Parameter
Cores
Cross section range
Type
Diameter
Length
Conductor
Insulation
Minimum voltage rating Uo/U
Minimum test voltage
Ambient temperature range
12.19.4

AC auxiliary power cables

Parameter
Number of cores
Cross section range
Shielding
Conductor
Insulation
Minimum voltage rating (Uo/U)
Minimum test voltage (AC)
Ambient temperature range
Strip length
96
Note: PE cable from power cabinet to power cabinet and from power
cabinet to charge post (associated with DC wires) and for PE grounding
electrodes.
Specification
6 kV
-40°C to 80°C (-40 °F to 176 °F)
+90°C (+194 °F)
6x outer diameter
Specification
1 core, green
35 mm² (69 kcmil) (2 AWG)
Flexible, unshielded
10 to 17 mm (0.39 to 0.67 in)
Refer to the local rules.
Fine strand copper wire according to
VDE 0295 Cl. 5/ IEC 60228 Cl. 5
Special PVC that is serviceable for out-
door use, UV-protected, and oil resistant
600 V
4 kV
-40°C to +80°C (-40 °F to +176 °F)
Specification
4
2.5 mm² (14 AWG)
No
Bare copper, fine wired, brunch stranded
according to VDE 0295 CI.5/IEC CI.5
Special PVC ( that is serviceable for out-
door use, UV-protected, and oil resistant
600 V
4 kV
-40°C to +80°C (-40 °F to +176 °F)
11 mm (0.43 in)
9AKK107992A3069-EN | 004