Connecting Flow Meters With Two Groundings; Connecting The Digital Output - INTEGRA Metering CALEC ST III User Manual

Standard & smart multi-protocol heating and cooling energy calculator
Table of Contents

Advertisement

Installation
5.3.9

Connecting flow meters with two groundings

This option is only for CALEC® ST III Standard.
Disconnect CALEC® ST III from power supply.
u
Take off the front cover [}p. 20].
u
Take off the calculator.
u
Connect the green cable (1) to terminal 11 (-).
u
Connect the yellow cable (2) to terminal 10 (S).
u
Connect the blue cable (3) to the adapter with
u
the terminal OUT2- (GND).
Connect the brown cable (4) to the adapter with
u
the terminal OUT2+ (+).
Connect cable (5) to terminal N (OUT1-).
u
Connect cable (6) to terminal L (OUT1+).
u
Connect cable (7) to terminal IN- (GND).
u
Connect cable (8) to terminal IN+ (+24 VDC).
u
Plug in the calculator.
u
Close the front cover [}p. 20].
u
5.3.10

Connecting the digital output

Disconnect the CALEC® ST III from the power
u
supply.
Take off the front cover [}p. 20].
u
Connect the pulse output signals to terminal 50
u
and 51.
Close the front cover [}p. 20].
u
3-140-UM-EN-02
Wrong supply voltage
Wrong supply voltage may damage the adapter module.
Only use 24 VDC as supply voltage.
u
NOTICE
8
7