Connecting The Calec® St Iii Smart - INTEGRA Metering CALEC ST III User Manual

Standard & smart multi-protocol heating and cooling energy calculator
Table of Contents

Advertisement

Installation
5.3.2
Connecting the CALEC® ST III Smart
Connect the meter according to schematic diagram on the inside of the front cover.
u
Upper row
Label
Function
6
2
Temperature
Hot side (2/4 wires)
1
5
9
Sensor power +3.6 V
11
GND #1
10
Pulse input #1
25
M-Bus B
24
M-Bus A
B11
Socket #1
Channel 1
A11
B31
RS485 #1 B
A31
RS485 #1 A
B21
Socket #2
Channel 1
A21
65
Sensor power -24 V
64
Sensor power +24 V
L, N
Main power supply
3-140-UM-EN-02
Wrong connections may destroy the device
The function and the marking of the terminals A11/B11, A12/B12, A31/B31, A41/B41, A21/B21,
A22/B22 depends on the options installed in the device.
u
Carefully check the installed options and choose the correct connections.
Incomplete wiring of the temperature sensors
Incomplete wiring of the 2-wire temperature sensors may lead to false measurement results.
u
Always connect the 2-wire temperature sensors together with the four supplied wire
bridges.
NOTICE
NOTICE
Lower row
Label Function
8
4
Temperature
Cold side (2/4 wires)
3
7
86
Sensor power +3.6V
55
GND #2
54
Pulse input #2
51
Digital out A
50
Digital out A
B12
Socket #1
Channel 2
A12
B41
RS485 #2 B
A41
RS485 #2 A
B22
Socket #2
Channel 2
A22
25 / 56

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents