INTEGRA Metering CALEC ST III User Manual page 9

Standard & smart multi-protocol heating and cooling energy calculator
Table of Contents

Advertisement

Introduction
Additional functions
Heat- / cold meters eight tariffs
Data backup in the event of a
power failure
Adjustable low temperature differ-
ence ΔT cut-off (LFCO)
Limit value monitoring
Mains version
Power supply (Standard version)
Power supply (Smart version)
Calculation cycle
Backup battery real-time clock
Low voltage power supply for flow meters
Supply voltage (Standard & Smart
version)
Supply voltage (only on Smart ver-
sion)
3.6 V sensor power output
24 V sensor power output
Pulse inputs
Input #1 (10/11)
Input #2 (54/55)
3-140-UM-EN-02
This option allows the management of up to eight different tariffs
with reference temperature control. The measurement is split into
different registers.
In EERPOM >10 years
Function for stopping the energy calculation when the temperature
difference is too low, ΔT LFCO adjustable ΔT = 0-2.99 K.
One-sided or two-sided, hysteresis 0 – 10 %, action of the output
signal is selectable.
1 W / 24 VAC/DC – 240 VAC, 50/60 Hz (according to EN 1434).
5W / 110 – 240 VAC, 50/60 Hz (according to EN 1434)
1 s
3 V Li-Mn CR1220
Voltage
2x 3.6 VDC, max. 2 mA
galvanic isolation max. 48 VDC
1x 24 VDC, max.150 mA
galvanic isolation max.48 V DC
Power supply, galvanically isolated to the system, for external flow
meters.
V
out nom
V
OUT min
V
OUT max
I
Out min
V
Ripple
Load regulation
Insulation voltage galvanic isola-
tion
Clearance to other circuits
Power supply, galvanically isolated to the system, for external loads
or flow meters.
V
out nom
V
OUT min
V
OUT max
I
Out min
V
Ripple
Load regulation
Insulation voltage galvanic isola-
tion
Clearance to other circuits
Connecting a pulse generator according to NAMUR, with potential-
free contact (reed relay) or SSR (solid state relay), or for active sen-
sors with the following values.
Flow meter
e.g. AMFLO® SONIC UFA 113
e.g. AMFLO® MAG Smart or ac-
tive sensors
3.6 V
3.45 V
3.75 V
10 mA
50 mV
±1 % @ load steps of 5 mA
Normative 48 V
technical: 312 VAC
0.5 mm
24 V
22 V
26 V
180 mA
200 mV
±6 % @ load steps of 100 mA
Normative 48 V
Technical: 312 VAC
0.5 mm
9 / 56