Electrical Installation - INTEGRA Metering CALEC ST III User Manual

Standard & smart multi-protocol heating and cooling energy calculator
Table of Contents

Advertisement

Installation
5.3

Electrical installation

The device is equipped with screw terminal connectors. Stripped rigid conductors or flexible conductors with
crimped ferrules (AEH) can be plugged directly into the screw terminal
Connectable conductors:
Wire range (rigid or flexible): 1.0...2.5 mm
l
Stripping length: 6-7 mm
l
AWG 28-12
l
The functionality of different connections depends on the installed modules and the activated options.
3-140-UM-EN-02
Electric shock
Touching energized system parts can cause immediate death or serious injury.
Make sure that installation work is only carried out by authorized specialists.
u
Before carrying out any work on the system, disconnect the power supply and check that
u
no voltage is present.
If an insulation is damaged, disconnect the power supply immediately and arrange for im-
u
mediate repair.
DANGER