Installation
BACnet
Module #1: A11/B11 (Channel #1)
When installing CALEC® ST III at the end of the BACnet segment the internal termination resistor can be
Disconnect the CALEC® ST III from the power
u
supply.
Take off the front cover [}p. 20].
u
If module #1 is installed: Connect BACnet to ter-
u
minals A11 (+) and B11 (-).
If module #2 is installed: Connect BACnet to
u
terminals A21 (+) and B21 (-).
Close the front cover [}p. 20].
u
Apply voltage.
u
For the programming options to this module see
BACnet [}p. 45].
N2Open
Module #1: A11/B11 (Channel #1)
When installing CALEC® ST III at the end of the N2Open segment, the internal termination resistor can be
u
Disconnect the CALEC® ST III from the power
supply.
Take off the front cover [}p. 20].
u
If module #1 is installed: Connect N2Open to
u
terminals A11 (+) and B11 (-).
If module #2 is installed: Connect N2Open to
u
terminals A21 (+) and B21 (-).
Close the front cover [}p. 20].
u
Apply voltage.
u
For the programming options to this module see N2-
Bus [}p. 45].
LON
Module #1: A11/B11 (Channel #1)
32 / 56
The interface is electrically isolated.
used.
Factory settings:
Manufacturer ID: 431
BACnet device profile: B-ASC
BACnet MAC address: Last 2 digits of the serial number
Device instance number: Last 5 digits of the serial number
Mode: Master
Baud rate: Automatic
The interface is electrically isolated.
used.
Factory settings:
N2Open address: 1
Baud rate: 9'600 Baud
The interface is electrically isolated.
Module #2: A21/B21 (Channel #1)
Module #2: A21/B21 (Channel #1)
Module #2: A21/B21 (Channel #1)
3-140-UM-EN-02