INTEGRA Metering CALEC ST III User Manual page 10

Standard & smart multi-protocol heating and cooling energy calculator
Table of Contents

Advertisement

Introduction
Pulse inputs
Pulse input class ID
Pulse outputs
Output #1 (50/51)
Pulse output
M-Bus (on-board or option)
M-Bus interface
Addresses
Baud rate
wM-Bus (on-board or option)
wM-Bus interface
Frequency band
Addresses
Modbus RTU (option)
Physical layer and address
Baud rate
Address range (slave)
Parity
Function code
LON interface (option)
Type
Baud rate
Max. bus length
BACnet MS/TP (option)
Physical layer and AMT ID
BACnet device profile and instance
BACnet MAC address
Baud rate and mode
10 / 56
2-wire pulse input according to class ID compliant with EN1434-2
Suitable for NAMUR-, "Open Collector" or mechanical pulse sources
Supply voltage
Source impedance
Switching threshold IL
Switching threshold IH
Pulse length
Pulse pause
Max. pulse frequency
Typical input capacitance
Passive digital output
Contact rating
Electrical isolation
Contact resistance (on)
Contact resistance (off)
Pulse frequency
Pulse width
According to EN 13757-2/-3
Primary address: 0
Standard secondary address: 99999999
300, 2'400, 9'600 Baud
According to EN 13757-4 / OMS 4.0
868 MHz (T1 Mode)
OMS address including serial number of the device
RS 485 / address: 1
300, 2'400, 9'600, 19'200, 38'400 Baud
1...247
Even
03: Read holding register
LON TP-FT 10
Free topology (2-wire twisted pair)
Certified in accordance with LONMARK® 3.4
78 k Baud
500 m / 2700 m with/without termination resistors
64 nodes per segment
RS 485 / ID: 431
B - ASC / the last 5 digits of the serial number
The last 2 digits of the serial number
Automatic / master
8...8.4 V
1 kΩ
2.1 mA
1.2 mA
≥ 2 ms
≥ 2.5 ms
≤ 200 Hz
20 nF
48 VDC, 100 mA
48 V
<30 Ω
>10 MΩ
Max. 4 Hz
100 ms
3-140-UM-EN-02

Hide quick links: