Menu Structure; Counter; Info; Test - INTEGRA Metering CALEC ST III User Manual

Standard & smart multi-protocol heating and cooling energy calculator
Table of Contents

Advertisement

Operation
6.6

Menu structure

6.6.1

Counter

The depiction of fields in the menu structure depends on the respective options.
Display
E1
V1
M1
E2
V2
M2
E3
H1
H2
Imp
Sid
6.6.2

Info

This menu is only visible if an error is present. It displays the type of error as described in the table.
Display
SYSt-Err
U-Err
th-Error
tc-Error
MEM-Err
OPT-Err
th-ALArM
tc-ALArM
dt-ALArM
Ext-AL
AP-Err
SEAL-Err
6.6.3

Test

This menu is available for LCD test purposes.
6.6.4

Instant

Display
Th
Tc
3-140-UM-EN-02
Meaning
Energy meter reading
Volume meter reading
Mass meter reading (op-
tional)
Energy meter 2 reading (op-
tional BDE/TGR)
Volume meter 2 reading (op-
tional BDE)
Mass meter 2 reading
Energy meter 3 reading (op-
tional TGR)
Auxiliary counter 1 reading
(optional flow)
Auxiliary counter 2 reading
Pulse value of flow meter
Installation side of flow me-
ter
Meaning
Error system
Error supply
Error temperature sensor hot side
Error temperature sensor cold side
Error of internal memory EEPROM
Error on one of the option modules (HW)
Temperature on hot side outside the permitted range
Temperature on cold side outside the permitted range
Temperature difference outside the permitted range
External alarm
Communication problem between main board and calculator
MID seal broken
Meaning
Current temperature hot side
(for cooling = return flow)
Current temperature cold
side (for cooling = forward
flow)
Visible
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
According to calculator function
Visible
According to calculator function
According to calculator function
Editable
Programming mode
Programming mode
Programming mode
Programming mode
Programming mode
Programming mode
Programming mode
Service mode
Service mode
No
No
Editable
No
No
41 / 56

Hide quick links:

Advertisement

Table of Contents
loading