Electrical connection

Pulse output A and B setting

Install pulse cable through glands, before pushing printed circuit board back into place in base part. For compact version, install pulse
cables and power supply cable through gland without removing printed circuit board.
For AMFLO
SONIC UFA-280, pulse output A and B settings depend on the ordering: Normal factory settings, see the following table.
®
The approved AMFLO
®
SONIC UFA-280 settings cannot be changed according approval requirements, but it can be read out per software.
Output A
Output B
Pulse value A & B
(depending on DN value)
Pulse width
Pulse output A settings
Output A, terminals 56/57:
Pulse rate can be seen on transmitter side label and must correspond to pulse setting of energy calculator type.
Preset output B settings
Output B, terminals 66/67:
Preset to alarm indication – see Fig. 1:
Example: If track 1 is not measuring, a „triangle" alert appears
on display. Failure code „F1" appears in display menu 4,
and relay output terminals switch to „off".
Call up indication – see Fig. 2:
The call up output is active until manually reset by use of
software program. Call-up function is also activated when
alarm output function is activated.
A third possibility is to adjust output B as volume pulse output, e.g. reward pulses. Typically with the same settings as the forward pulses
(see table above).
AMFLO
SONIC UFA-280
®
AMFLO
®
SONIC UFA-280
Forward or reverse pulses
Preset: Forward
Forward or reverse pulses, alarm, call-up
Preset: Alarm
Preset: See scheme for AMFLO
®
or the following settings for CALEC ST energy calculator.
5 ms
Alarm output
Alarm status
Fig. 1
Call up output
Call up reset
Call up status
Fig. 2
SONIC UFA-280,
ON
OFF
Error
No error
On
Off
On
Off
29