GFK-2409B
Figure 87
6.2

Configuring PLC B

Open the Hardware Configuration for PLC_B_HW
In the Max-ON RX3i Project, select and expand the Hardware Configuration node of the
PLC_B_HW target.
Figure 88
Set the Max-ON RX3i Identity for PLC B
The identity for CPU B is determined by the value set in the Logic Checksum Words CPU
Parameter located in the CPU's Hardware Configuration for CPU B.
Open the CPU module's Hardware Configuration by double-clicking on the CMU310
module. Click on the Scan tab to display the Logic Checksum Words parameter.
Verify that the Logic Checksum Words parameter's value is 16. If it is not 16, change the
parameter to this value.
Configuring the Hot Standby Redundancy CPUs
Chapter 6
Oct 2019
80