Installation
4.3

Requirements on the technical room

The following minimum requirements must be met
before the cogeneration module is moved and installed
in the technical room:
-
The place where the cogeneration module is
installed should be level and have sufficient load
bearing capacity.
-
Provide sufficient space for carrying out
installation and maintenance work (Fig. 6).
-
The technical room should have water supply and
a floor drain with oil barrier.
-
A competent firm should check to see if extra
noise control measures are required.
-
If the cogeneration module is installed after prior
dismantling, this must be done by supplier
personnel to ensure that warranty is not lost.
-
The effects of external vibrations, e.g., transmitted
through the building, or electromagnetic radiation,
must be reduced to an absolute minimum and
documented at the time of start-up.
-
The room where it will be erected should be made
pursuant to the applicable firing directive and
applicable construction law ordinances/
regulations. We recommend integrating the CHP
module into the fire protection strategy for safe
operation.
-
To increase workplace safety for the operator we
recommend that you install a CO monitor in the
installation room.
CAUTION
Do not store or use flammable materials
or liquids near the Block-type thermal
power plant.
Do not smoke or use open fire or naked
flame during operation of the block-type
thermal power plant.
We recommend, similar to the
requirement of the old Heating Room
Directive, installing a fire extinguisher of
the appropriate size (at least 9 l) in the
technical room.
VITOBLOC 200 BM-366/437 Assembly instructions
NOTE
The following signs shall be put up both
outside and inside the technical room:
Prohibition sign P 06
"No access for unauthorized persons"
Prohibition sign P 02
"Fire, naked light and smoking not
permitted"
Prohibition sign P 11
"No access for persons wearing a
pacemaker"
19