Page 1
Assembly instructions for the specialist VITOBLOC 200 model BM-190/238 Part no. 7639779 Block-type thermal power plant for biogas operation Please store this document in a safe place. 5780045 GB 10/2017...
Page 2
These documents and the original conformity declaration are stored on the premises of the manufacturer. NOTE The Vitobloc 200 cogeneration module is not suited to 60 Hz operation which means that it is in particular not available to the American and Canadian market.
Condensate drainage ....................25 4.10 Electrical connection ....................26 4.11 Installation of the noise cover (if part of the supply) ..........27 Notification of readiness for start-up ..........28 Declaration of conformity according to Machine Directive ..34 VITOBLOC 200 BM-190/238 Assembly instructions...
This is the reason why only instructed specialist personnel are allowed to operate and maintain the plant. Assembly instructions VITOBLOC 200 BM-190/238...
Page 5
Opening of exhaust flanges Exhaust escape Exhaust lines Opening the measuring port Risk of poisoning Measuring port Touching unprotected exhaust pipes Risk of burning Touching unprotected measuring port Tab. 1 Block-type thermal power plant hazards VITOBLOC 200 BM-190/238 Assembly instructions...
Wear suitable protective clothing for work on the ignition system because a defective ignition cable can cause electric shock. This work must only be performed by specially trained technicians. Assembly instructions VITOBLOC 200 BM-190/238...
2014/30/EU (EMVG) EU electromagnetic compatibility directive Safety of machinery – Electrical equipment of machines DIN EN 60204-1 (VDE 0113-1) Part 1: General requirements Safety of machinery – Fundamental terminology, general design principles DIN EN ISO 12100 VITOBLOC 200 BM-190/238 Assembly instructions...
Page 8
VDI 3985 generating plants with internal combustion engines VDI 6025 Economic calculations for capital goods and plants Tab. 3 Important regulations, directives, norms and guidelines for the construction and operation of a block-type thermal power plant Assembly instructions VITOBLOC 200 BM-190/238...
10.2 maximum acceptable operating pressure at high temperature maximum acceptable operating pressure at low temperature pressure loss at standard flowthrough in the HT standard module pressure loss at standard flowthrough in the NT standard module VITOBLOC 200 BM-190/238 Assembly instructions...
Page 10
Ambient temperature no higher than 35°C and its average value over a period of 24 hours no higher than 30°C Tab. 4 Operating parameters of the complete cogeneration module Vitobloc 200 BM-190/238 Assembly instructions VITOBLOC 200 BM-190/238...
Exhaust connection (AGA) from cogeneration module, pipe connection DN 150 / PN10 Condensed water connection (KO), pipe connection Pipe ø 22 x 2.0 Heating water flow/return (HV/HR), pipe connection DN 65 / PN16 Gas connection (GAS), pipe connection DN 65 / PN16 VITOBLOC 200 BM-190/238 Assembly instructions...
Page 12
External control engineering makes the selection for stand-by operation after the customer’s load shedding. The selection can be made automatically inside of the module, but without monitoring load shedding. Tab. 5 Specifications of the complete cogeneration module Vitobloc 200 BM-190/238 Assembly instructions VITOBLOC 200 BM-190/238...
Flange 580 x 580 P20 cogeneration modules Vitobloc 200 BM-190/238 have optional noise covers and extract fans. For minimum 20 mbar gas flow pressure and 5 kW/nm³ calorific value, other values on request Tab. 6 Dimensions, weights, finishes and connections Fig.
Block-type thermal power plant storage conditions The block-type thermal power plant should be transported and stored protected from moisture (max. rel. humidity: 70 %). Do not expose the cogeneration module to air with dust or halogens. Assembly instructions VITOBLOC 200 BM-190/238...
It is necessary to use a transport frame when transporting and putting into place a cogeneration module without a sound- absorbing hood (can be hired out against a deposit). VITOBLOC 200 BM-190/238 Assembly instructions...
CAUTION Make sure that the foundation base has the required height (≥ 150 mm) for drainage of condensed water. Minimum base size for Vitobloc 200 BM-190/238 3,600 mm 1,600 mm 150 mm Fig. 4 block-type thermal power plant with base...
1,100 mm from the basic frame if not transported 1,650 mm vertically, which can endanger the 3,850 mm transport personnel. Tab. 7 Minimum distances in the technical room VITOBLOC 200 BM-190/238 Assembly instructions...
All safety devices must comply with local requirements. All accident prevention rules shall be observed. Scope of delivery Module Optional equipment as ordered Assembly instructions VITOBLOC 200 BM-190/238...
We recommend, similar to the requirement of the old Heating Room Directive, installing a fire extinguisher of the appropriate size (at least 9 l) in the technical room. VITOBLOC 200 BM-190/238 Assembly instructions...
44 (GAS) PZA+ PZA- Fig. 8 Monitoring devices of the Vitobloc 200 BM-190/238 version with separate low-temperature circuit If the system pressure in the mixture cooling water circuit (17+18) exceeds 2 bar, the customer should provide hydraulic separation. Overall legend:...
Use a weather protection grill with sufficient size of openings to prevent flow noise due to restriction of section (noise protection). If special noise requirements apply, install a sound trap each in the fresh air and extract systems. VITOBLOC 200 BM-190/238 Assembly instructions...
24 V direct voltage (battery supply). Also observe the requirements of DVGW Code of Practice G 260. ● Connect the block-type thermal power plant to the available gas supply system by a branch line. VITOBLOC 200 BM-190/238 Assembly instructions...
Gully with water seal Fig. 12 Scheme showing the peripheral exhaust gas system of two cogeneration modules with condensed water drain pipe and drainage of safety valves (dimensions in mm) Assembly instructions VITOBLOC 200 BM-190/238...
CHP module (in the scope of delivery) Since the oil gas can condensate in the exhaust gas at low exhaust gas temperatures, the customer should provide an oil trap in the condensate discharge. VITOBLOC 200 BM-190/238 Assembly instructions...
● For guidelines concerning the dimensioning of cables and fusing by buyer, cf. page 12 Tab. 5 „Specifications of the cogeneration module“ Assembly instructions VITOBLOC 200 BM-190/238...
Press on the sound-absorbing hood Turn the spanner another 90° while turning the spanner another 90° (the dot marks on the lock are now (the dot marks on the lock are now 180° to one another) opposite one another) VITOBLOC 200 BM-190/238 Assembly instructions...
(no earlier than 4 weeks after notice of readiness): ________________________________________ Other comments: We are aware that Viessmann Kraft-Wärme-Kopplung GmbH will not be liable for losses or deviations from design values that result from deviating operating conditions. We (the client) will bear all additional costs in full that result from commissioning having to be terminated on account of on-site defects, such as missing installations, connections, operating fluids and other installation work in the installation room.
Page 29
(siphon height ≥ 250 mm) □ plastic (with STB) The type of waste gas plant: □ stainless steel The manufacturer of the waste gas plant: ________________________ Number of sound absorbers: ________________________ Confirmation of the installation specialist Page 3 VITOBLOC 200 BM-190/238 Assembly instructions...
Page 30
Type of gas supply: Natural gas / biomethane (LPG operation only permissible with module types □ Vitobloc 200 EM-6/15, EM-9/20 and EM-20/39 R2) LPG (propane) The gas supply to the Block-type thermal power plant is secure. □ The integration of the gas equipment complies with European norms and yes _________________ directives and with the planning and installation instructions.
Page 31
GPSG (Product Safety Act) Article 4(4)]: The exhaust gas system complies with DIN V 18160-1 / pressure class H1. (5,000 Pa gauge pressure / 0.006 l/s m² leak rate) Specialized stack construction firm: Date Stamp Signature VITOBLOC 200 BM-190/238 Assembly instructions...
Page 32
Name: _____________________________ Tel. No.: ___________________ Proposed system maintenance / HVAC firm: Name: _____________________________ Tel. No.: ___________________ Contact of the local power supply company: Name: _____________________________ Tel. No.: ___________________ Address of the local power supply company: _____________________________________________________________ Assembly instructions VITOBLOC 200 BM-190/238...
Page 33
yes no Customer's mains tie circuit breaker actuation yes no Mains tie circuit breaker actuation by module Mains tie circuit breaker actuation by Viessmann yes no process control system (MMM) yes no...
Declaration of conformity according to Machine Directive Declaration of conformity according to Machine Directive Assembly instructions VITOBLOC 200 BM-190/238...