Transportation
3.4
Setting up
●
The cogeneration module is installed on a raised
base without separate anchoring and placed on
sylomer strips (loose supply) for separation from
structure-borne noise.
CAUTION
Make sure that the foundation base has
the required height (≥ 150 mm) for
drainage of condensed water.
H
W
Base minimum dimensions
Vitobloc 200 BM-366/437
L
4,000 mm
W
1,600 mm
H
150 mm
Fig. 4
block-type thermal power plant with base
380
540
Switching
cabinet
side
Fig. 5
Locating plan for sylomer strips
16
L
3600
2660
1600
• The scope of delivery includes:
10 green SR 55 sylomer strips
2 yellow SR 11 sylomer strips
(1,500 x 100 x 50 mm)
• blank required green:
7 x 1,500 mm long
2 x 1,400 mm long
1 x
1 x
• blank required yellow:
1 x 1,500 mm long
1 x
1 x
Assembly instructions VITOBLOC 200 BM-366/437
600 mm long
300 mm long
380 mm long
280 mm long