Operating Instructions
for use by heating contractor
Vitotronic 200-H, type HK1B
Weather-compensated heating circuit control unit
VITOTRONIC 200-H
Certified as a component
part for Viessmann boilers
5693 986 - 01 02/2015
Product may not be exactly as shown
IMPORTANT
Read and save these instructions
for future reference.
Please file in Service Binder

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITOTRONIC 200-H

  • Page 1 Operating Instructions for use by heating contractor Vitotronic 200-H, type HK1B Weather-compensated heating circuit control unit VITOTRONIC 200-H Product may not be exactly as shown IMPORTANT Read and save these instructions Certified as a component for future reference. part for Viessmann boilers...
  • Page 2: Safety, Installation And Warranty Requirements

    Information contained in this and installation of carbon monoxide detectors. Follow the related product documentation must Viessmann maintenance schedule of the boiler contained be read and followed. Failure to do in this manual. so renders the warranty null and void.
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Vitotronic 200-H, HK1B Operating Safety Safety, Installation and Warranty Requirements....2 Product documentation...........2 Licensed professional heating contractor....2 Advice to owner............2 Warranty...............2 Safety Terminology............2 General Commissioning............5 Your System is Preset at the Factory......5 Tips on Saving Energy..........6 Controls..............7...
  • Page 4 Table of Contents Vitotronic 200-H, HK1B Operating Page Further Adjustments Entering Names for the Heating Circuit......24 Changing the Standard Menu........24 Selecting the Language..........25 Setting the Time and Date.........25 Setting the Temperature Unit ( F)......25 Restoring the Factory Settings........25 Scanning Information..........26 Scanning Fault Messages...........27...
  • Page 5: Commissioning

    General Vitotronic 200-H, HK1B Operating Commissioning The commissioning and matching of the control unit to local conditions and building characteristics, as well as instructing the user in the operation of the system, must be carried out by your heating contractor.
  • Page 6: Tips On Saving Energy

    General Vitotronic 200-H, HK1B Operating Tips on Saving Energy Utilize the setting options for the control unit and remote control (if installed): H Never overheat your rooms. Every degree by which the room temperature is reduced saves up to 6% on heating costs.
  • Page 7: Controls

    Operation Vitotronic 200-H, HK1B Operating Controls You can change any settings on your heating system centrally at the programming unit of the control unit. If remote controls are installed in your rooms, you can also adjust the settings at the remote controls.
  • Page 8: Standard Menu

    Operation Vitotronic 200-H, HK1B Operating Menu There are two control levels available, the “Standard menu” and the “Extended menu”. The menu overview can be found on page 32. Standard menu Call up the standard menu as follows: H If the screen saver is active (see page 9) Press OK.
  • Page 9: Extended Menu

    Operation Vitotronic 200-H, HK1B Operating Menu (continued) Extended menu Call up the extended menu as follows: H If the screen saver is active: Press OK and then H From anywhere in the menu: Press Note: Your heating contractor can block the use of the extended menu.
  • Page 10 Operation Vitotronic 200-H, HK1B Operating How to Use the Controls (continued) (if equipped with extension for heating circuits 2 & 3)
  • Page 11: Starting The Heating Circuit Control Unit

    Start-up/Shutdown Vitotronic 200-H, HK1B Operating Starting the Heating Circuit Control Unit Controls with open flap For flap, see page 7. 1. Switch the ON/OFF switch (see diagram) ON. Legend 2. Switch the ON/OFF switch ON. After a short time, A ON indicator (green)
  • Page 12: Shutting Down The Heating Circuit Control Unit

    Start-up/Shutdown Vitotronic 200-H, HK1B Operating Shutting Down the Heating Circuit Control Unit With frost protection monitoring For every heating circuit, select the heating program “Standby mode”. H No central heating. H No DHW heating. H Frost protection for the heating circuits and the DHW tank is active.
  • Page 13: Required Settings (Central Heating)

    Central Heating Vitotronic 200-H, HK1B Operating Required Settings (Central Heating) If you want central heating, check the following points: H Have you selected the heating circuit? For settings, see the next chapter. H Have you set the required room temperature? For settings, see page 14.
  • Page 14: Setting The Room Temperature

    Central Heating Vitotronic 200-H, HK1B Operating Selecting a Heating Circuit (continued) Note: If you return to the standard menu with the header will again display “HC1” (see page 8). For changes to the heating circuit display in the standard menu, see page 24.
  • Page 15: Setting The Heating Program For Central Heating

    Central Heating Vitotronic 200-H, HK1B Operating Setting the Heating Program for Central Heating Factory setting: “Heating and DHW” For the heating circuit displayed in the header Proceed as described on page 12. For the other heating circuits Extended menu 2. “Heating”...
  • Page 16: Changing The Heating Curve

    Central Heating Vitotronic 200-H, HK1B Operating Setting the Time Program for Central Heating (continued) Example shown: H Time program for Monday to Friday (“Mo-Fr”) H Time phase !: From 05:00 to 08:30 h H Time phase ?: From 16:30 to 23:00 h...
  • Page 17: Stopping Central Heating

    Central Heating/Comfort and Energy Saving Functions Vitotronic 200-H, HK1B Operating Stopping Central Heating For the heating circuit displayed in the header Standard menu for the heating program “Only DHW” (summer mode, no central heating) “Standby mode” (frost protection monitoring). OK to confirm.
  • Page 18: Select Comfort Function "Economy Mode

    Comfort and Energy Saving Functions Vitotronic 200-H, HK1B Operating Selecting Energy Saving Function “Economy Mode” To save energy, you can reduce the room temperature in standard heating mode. For example, if you leave your home for a few hours. Extended menu 2.
  • Page 19: Required Settings (Dhw Heating)

    Comfort and Energy Saving Functions/DHW Heating Vitotronic 200-H, HK1B Operating Selecting Energy Saving Function “Holiday Program” (continued) The holiday program starts at 00:00 h the day following your departure and ends at 00:00 h on the day of your return. This means the selected time program is active on the days of departure and return (see page 15).
  • Page 20: Setting The Dhw Temperature

    DHW Heating Vitotronic 200-H, HK1B Operating Setting the DHW Temperature Extended menu 2. “DHW” 3. “Set DHW temperature” 4. Set the required value. Setting the Heating Program for DHW Heating Extended menu 2. “Heating” 3. Select the heating circuit, if necessary (see page 13).
  • Page 21 DHW Heating Vitotronic 200-H, HK1B Operating Setting the Time Program for DHW Heating (continued) Extended Menu 2. “DHW” 3. “DHW time prog” 4. “Individual” 5. Select part of the week or a day. 6. Select the time phase !, ?, § or $.
  • Page 22 DHW Heating Vitotronic 200-H, HK1B Operating Setting the Time Program for DHW Heating (continued) Heating system with DHW circulation pump For further information about the DHW circulation pump, see chapter “Terminology”. H Automatic mode is set for the DHW circulation pump time program.
  • Page 23: Stop Dhw Heating

    DHW Heating Vitotronic 200-H, HK1B Operating Stopping DHW Heating You do not want to have DHW or heat your rooms. For the heating circuit displayed in the header Standard menu for the heating program “Standby mode” (frost protection monitoring). OK to confirm.
  • Page 24: Entering Names For The Heating Circuit

    Further Adjustments Vitotronic 200-H, HK1B Operating Entering Names for the Heating Circuits You can give heating circuits 1, 2 and 3 (“HC1”, “HC2” and “HC3”) individual names. The abbreviations “HC1”, “HC2” and “HC3” will be retained. Extended menu 2. “Settings”...
  • Page 25: Selecting The Language

    Further Adjustments Vitotronic 200-H, HK1B Operating Selecting the Language Extended menu 2. “Settings” 3. “Language” 4. Select the required language. Setting the Time and Date The time and date are factory-set. If your heating system has been shut down for a long time, it may be necessary to set the time and date.
  • Page 26: Scanning Information

    Scanning Vitotronic 200-H, HK1B Operating Scanning Information Subject to the connected components and settings made, you can scan current temperatures and operating conditions. The extended menu splits the information into groups: H “General” H “Heating circuit 1” H “Heating circuit 2”* H “Heating circuit 3”*...
  • Page 27: Scanning Fault Messages

    Scanning Vitotronic 200-H, HK1B Operating Scanning Fault Messages  If any faults have occurred in a boiler, the symbol flashes on the display and “Fault” is shown. The red fault indicator also flashes (see chapter “Starting the heating system”). 1. You can call up the cause of the fault with OK.
  • Page 28: Rooms Are Too Cold

    Troubleshooting Vitotronic 200-H, HK1B Operating Rooms are Too Cold Cause Remedy The heating system or heating circuit control - Switch the ON/OFF switch ON (see diagrams from page 11). unit is switched off. - Switch ON the mains isolator, if installed (outside the boiler room).
  • Page 29: The Dhw Is Too Hot

    Troubleshooting Vitotronic 200-H, HK1B Operating The DHW is Too Hot Cause Remedy The control unit is incorrectly set. Check and correct the DHW temperature if required (refer to the Installation Instructions) DHW heating is carried out by the solar thermal system.
  • Page 30: Flashes And "Fault" Is Displayed

    Troubleshooting Vitotronic 200-H, HK1B Operating “ ” Flashes and “Fault” is Displayed  Cause Remedy Heating circuit control unit fault. Proceed as described on page 27. “Controls Locked out” is Displayed Cause Remedy This function is disabled. Your heating contractor can lift this block.
  • Page 31: Maintenance

    H On back flushing filters, back flush every two months. Damaged connecting cables If connecting cables of the appliance or externally installed electrical accessories are damaged, replace them with special connecting cables. Replace only with Viessmann cables. Contact your local heating contractor.
  • Page 32: Menu Overview

    Additional Information Vitotronic 200-H, HK1B Operating Menu Overview Extended menu Heating Solar energy Set DHW temperature Information DHW time prog DHW circ time prog Settings Party mode General Heating circuit 1 HC1 Economy mode Detailed scan Set room temperature Heating circuit 2 HC2*...
  • Page 33 Additional Information Vitotronic 200-H, HK1B Operating Menu Overview (continued) Scanning options in the extended menu Note: Subject to the actual heating system equipment level, not all of the scans listed here may be available. You can scan more details on information marked with .
  • Page 34: Terminology

    Additional Information Vitotronic 200-H, HK1B Operating Terminology Balanced flue operation Setback mode (reduced heating mode) The combustion air is drawn from outside the building. See “Reduced heating mode”. Reduced heating mode Heating program When you are out or during the night, you can heat With the heating program you determine whether you the rooms in reduced heating mode (setback mode).
  • Page 35 Additional Information Vitotronic 200-H, HK1B Operating Terminology (continued) Heating curve Heating curves illustrate the relationship between the outside temperature, room temperature (set value) and boiler water or (heating circuit) supply temperature. The lower the outside temperature, the higher the boiler water temperature or heating circuit supply temperature.
  • Page 36 Vitotronic 200-H, HK1B Operating...