VITOBLOC 200 Block-type thermal power plant – electricity and heat from natural gas and biogas Very efficient due to cogeneration Total efficiency 96% Primary energy savings to 30,74% Technical Description CHP switching cabinet VITOBLOC 200 model EM-50/81 Block-type thermal power plant for...
Page 2
These documents and the original conformity declaration are stored on the premises of the manufacturer. NOTE The Vitobloc 200 cogeneration module is not suited to 60 Hz operation which means that it is in particular not available to the American and Canadian market.
Analog measurement converter (analog box) ............12 Control, measuring and regulating unit ..............13 Modes .......................... 18 Parameters ........................19 Description of the RS 3964-interface ................. 20 Terminal assignment for the CHP module control field ....25 Index ....................34 VITOBLOC 200 CHP switching cabinet...
Tab. 1 Equipment and dimensions USER NOTE Design in accordance with DIN VDE 0660, Part 500 and DIN 6280 Part 7, for ambient temperatures from 0° C to + 40° C and 70% relative humidity. CHP switching cabinet VITOBLOC 200...
160 kW 250 kW 400 kW 560 kW 3 times 120/0.05 A 120/0.05 A 300/0.05 A 500/0.05 A 800/0.05 A 1,000/5A and 3 special current transformers 5/0.05A Tab. 4 Power circuit for various cogeneration modules CHP switching cabinet VITOBLOC 200...
(operational values) automatic U-I (voltage and current values) menu level (selecting levels 2, 3, EVU and FACTORY – only with password) fault messages reset fault acknowledgement Tab. 8 Assignment of the function keys VITOBLOC 200 CHP switching cabinet...
Page 10
FACTORY level showing and changing all factory parameters Specific passwords are only issued to authorised persons (such as start-up personnel, service personnel or operators). Assignment of function keys , Part 1 – F1-F6 Tab. 9 CHP switching cabinet VITOBLOC 200...
Page 11
(OPTIONAL) line protection malfunctioning Tab. 10 Assignment of function keys , Part 2 – service menu and F7 VITOBLOC 200 CHP switching cabinet...
PT 100 mixed cooling water temperature PT 100/6 PT 100 exhaust gas temperature B NiCrNi exhaust gas temperature C NiCrNi exhaust gas temperature D NiCrNi load pressure (Option) 4–20 mA Tab. 12 Analog measurement converter CHP switching cabinet VITOBLOC 200...
Page 14
10 V) to the governor. Speed monitoring generates the two malfunctions below in the case of an unacceptable deviation from the appropriate limit: overspeed speed <50 Upm or pick-up defective Tab. 15 Description of the functions, Part 1 – mains, alternator voltages, alternator current monitoring and speed regulation or monitoring CHP switching cabinet VITOBLOC 200...
Page 15
– maximum cooling water temperature – maximum exhaust gas temperature – minimum exhaust gas temperature (sensor short-circuit) Tab. 16 Description of the functions, Part 2 – synchronising, oil pressure, oil levels, cooling water, exhaust gas and alternator temperature monitoring VITOBLOC 200 CHP switching cabinet...
Page 16
The step motor is triggered via two digital contacts. The pulse-interval ratio is adjustable just like all targets and limits (level 3). Tab. 17 Description of the functions, Part 3 – output regulation and monitoring, temperature controller, module deselect and select after temperature and lambda regulation CHP switching cabinet VITOBLOC 200...
Page 17
14. alternator contact on 15. output regulation active 16. lambda regulation active 17. cogeneration module in operation Tab. 18 Description of the functions, Part 4 – gas monitoring, enabling in stand-by operation and start-stop process changes VITOBLOC 200 CHP switching cabinet...
The "Voltages" item on the menu shows the mains voltage, alternator voltage and busbar voltage with their frequencies. Pressing the F2 key twice shows the cooling water temperature and temperature sensors PT 100/2 and PT 100/3. Tab. 20 Historical memory and options CHP switching cabinet VITOBLOC 200...
39. offset oil pressure potential adjustment if there are analog parameter differences 40. offset battery voltage potential adjustment if there are analog parameter differences Tab. 21 Parameter, Part 1 – level 3 VITOBLOC 200 CHP switching cabinet...
102 bytes to remote service. Section data item list CHP UNI 001 describes the structure of the data block from page 21. Tab. 23 Interface parameters and DK3964R data request CHP switching cabinet VITOBLOC 200...
Page 21
Tab. 24 Data item list, Part 1 – internal module values VITOBLOC 200 CHP switching cabinet...
Page 22
L3 total mains voltage total alternator voltage total alternator current output network frequency alternator frequency spare spare CosPhi spare spare Tab. 25 Data item list, Part 3 – analog values and line protection CHP switching cabinet VITOBLOC 200...
Page 23
ON knocking OFF timer deselect message timer release message network breakdown F < warning network breakdown F > warning network breakdown U+F <> warning minimum knocking output VITOBLOC 200 CHP switching cabinet...
Page 24
Tab. 26 List of fault messages customer’s control equipment hardware to guarantee The customer should couple it to the computer it meets the operator’s hardware and convenience (RK512 or other) for establishing communication between the cogeneration hardware and the requirements. CHP switching cabinet VITOBLOC 200...