VAT 642 GP Series Installation, Operating, & Maintenance Instructions page 65

Table of Contents

Advertisement

Series 642
Command
®
(DeviceNet
term
if deviant)
LEARN STATUS
(calibration state)
Unless otherwise specified all values in the table above are in decimal notification. Hexadecimal values
are indicated by the letter 'h' (e.g. 31h)
605593EC
INSTALLATION
Service Code
Class ID
Get
14
51
This command returns the status of the LEARN procedure. The status is binary coded.
Bit
Explanation:
(LSB) 0
0 = LEARN not running
1 = LEARN running
1
0 = LEARN data set present
1 = LEARN data set not present
2
0 = ok
1 = LEARN terminated by user
3
0 = ok
1 = pressure in position OPEN
> 50% sensor full scale
or
> LEARN PRESSURE LIMIT
4
0 = ok
1 = pressure in position 0
< 10% sensor full scale
5
0 = ok
1 = pressure falling during LEARN
6
0 = ok
1 = sensor not stable during LEARN
7
reserved
8
reserved
9
reserved
10
0 = ok
1 = LEARN terminated by controller
11
0 = ok
1 = pressure in position OPEN negativ
12
reserved
13
reserved
14
reserved
15
reserved
(MSB) 16
reserved
Edition 2017-11-24
Instance ID
Attribute ID
Description
1
106
(of high range sensor in case of a 2 sensor system)
(of low range sensor in case of a 2 sensor system)
Service
Service
data length
data field
(number of bytes)
2
65/113

Advertisement

Table of Contents
loading

Table of Contents