Preparation For Initial Start-Up; Figure 15: Ups Circuit Breakers With Protective Covers - Gamatronic uPS 3:3 Phase Series User Manual And Instruction Manual

10kva (gems)
Table of Contents

Advertisement

Gamatronic Electronic Industries Ltd.
3.3.3

Preparation for Initial Start-Up

To prepare the UPS for initial start-up:
The UPS has five main circuit breakers, at the rear of the unit.
1.
INPUT CHARGER
ST/SW (Static-Switch)
OUTPUT
BATTERY C.B. (in horizontal position)
MAINTENANCE BYPASS (covered by a separate metal plate)
Verify that ALL the circuit breakers are turned OFF and that the
protective covers have not been removed (see Figure 15).

Figure 15: UPS Circuit Breakers with Protective Covers

Verify that the circuit breaker in the mains electrical cabinet supplying
2.
the UPS is OFF. No voltage should exist in the cables.
µPS Series 3:3 Phase 10kVA (GEMS)
BATTERY C.B.
CABLE TIE
User Guide
MAINTENANCE
BYPASS COVER
Page 19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents