Item
Parameter
Fault history batch clear
Parameter clear
All parameter clear
Inverter reset
Read/
Code
write
number
• Refer to the instruction code in the Instruction Manual (Detailed) of the inverter to read
H00 to
and write as required.
Read
H63
Write to Pr.77 and Pr.79 is disabled.
When setting Pr.100 and later, set link parameter extended setting.
• Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
• When changing the parameter values frequently, set "1" in Pr.342 to write them to the
H80 to
Write
RAM. (Refer to the Instruction Manual (Detailed) of the inverter for the details of
HE3
Pr.342.)
Write
HF4
H9696: Clears the fault history as a batch.
All parameters return to the initial values.
Whether communication parameters are also cleared or not depends on the data.
(: Cleared, : Not cleared)
Refer to the Instruction Manual (Detailed) of the inverter for Parameter clear, All
parameter clear, and communication parameters.
Clear command
Write
HFC
Parameter clear
All parameter
clear
When clear is executed with H9696 or H9966, communication parameters also return to
the initial values. When resuming operation, set the parameters again.
Executing clear will clear the instruction code HEC, HF3, and HFF settings.
Write
HFD
H9696: Resets the inverter.
Description
Data
Communication Pr.
H9696

H5A5A

H9966

H55AA

Details of remote input and output signals
7
81