• Operation at error removal
Fault description
Pr.502 setting
0
1, 11
Communication line
2, 12
3
4
0, 3
Communication option
1, 2, 11, 12
itself
4
When the communication error is removed during deceleration, the motor re-accelerates.
Under position control, the motor does not re-accelerates even when the communication error is removed during deceleration.
• The motor is decelerated to a stop according to the setting of Pr.111 Third deceleration time when an error occurs while
Pr.502 = "11 or 12". (Only for the FR-A800 series)
Pr.502 setting
0
Output shutoff
1 to 4
Deceleration stop according to the selected deceleration time (selectable using the RT or X9 signal)
11, 12
Deceleration stop according to the setting of Pr.111
42
INVERTER SETTING
Operation
Output stop status
"
E.OP1
continues.
Restart
Normal
Normal
Output stop status
"
E. 1
continues.
Continues operation with
"CF" warning
the Pr.779 setting.
Operation to a stop at a communication error occurrence
Indication
Fault output
"
kept
Kept provided
Not output
"
Kept provided
kept
Not output