NOTE
• Set the station number switches before turning ON the inverter. Do not change the setting while the power is ON.
Doing so may cause an electric shock.
• Set the switch exactly onto one of the numbers. Otherwise normal data communication cannot be established.
• Set a unique station number. (If different devices have the same station number, communication cannot be performed
properly. If an error occurs due to a duplicated number, assign the station number correctly, then reset the master or
the inverter power.)
• Station numbers do not have to be consecutive numbers.
• The station number switch setting can be displayed on the operation panel when "45" is set in Pr.52 Operation panel
main monitor selection.
 Setting the IP address with parameters (Pr.434 to Pr.437)
Set the station number switches to "0 (H00) or 255 (HFF)" to specify the IP address of the inverter using Pr.434 to Pr.437.
The setting is applied after an inverter reset or at the next power-ON.
IP address
First octet
Pr.434
Second octet
Pr.435
Third octet
Pr.436
Fourth octet
Pr.437
Good
Bad
example
example
Description
INVERTER SETTING
5
49

Advertisement

Table of Contents
loading