Festo CPX-4AE-4AA-H Operating Instructions Manual page 50

Input module
Hide thumbs Also See for CPX-4AE-4AA-H:
Table of Contents

Advertisement

Technical data
Characteristic
Storage temperature
Humidity (non-condensing)
Degree of protection in accordance with
EN 60529
Conformity
Information on materials
– Housing
Tab. 49: General technical data
Electrical data
Characteristic
Power supply
Nominal operating voltage
Operating voltage range
Intrinsic current consumption at nominal
operating voltage
Electrical connection
Reverse polarity protection
Analogue current channels
Number
Signal range
Repetition accuracy at 25 °C
Operating error limit related to the
ambient temperature range
Basic error limit at 25 °C
Analogue inputs
Input resistance
Open circuit voltage
Short circuit current
Available sensor voltage
50
Specification/value
[°C]
–20 ... 70
[%]
95
Depending on the connection block
è www.festo.com/sp
PA-reinforced
PC
Specification/value
[V DC]
24
[V DC]
18 ... 30
[mA]
Typically 170, max. 200
– M12, 4-pin
– Spring-loaded terminal
– Screw terminal
– For operating voltage
– Per channel for inputs and outputs
4, selectable as inputs or outputs
– 0 ... 20 without HART
[mA]
– 4 ... 20 without HART
– 4 ... 20 with HART
[%]
0.05
[%]
± 0.3
[%]
± 0.1
[Ω]
300
[V DC]
Max. 28.8
[mA]
Max. 22
[V]
Min. 20.7 at 20 mA
Festo — CPX-4AE-4AA-H — 2021-06b