Commissioning
Channel parameter: monitoring of channel 0 ... 3
– Bit 0: monitoring of lower critical limit
Allocation
– Bit 1: monitoring of upper critical limit
– Bit 2: monitoring of wire break (idling)
– Bit 3: monitoring of overflow/underflow
– Bit 4 ... 6: reserved
– Bit 7: monitoring of parameterisation errors
– Bit 0 ... 3:
Values
– Bit 7:
Tab. 19: Description of "Monitoring of channel 0 ... 3"
Channel parameter: lower critical limit of channel 0 ... 3
Function number
4828 + m* 64 + 11 (channel 0, low byte) 4828 + m* 64 + 12 (channel 0, high
byte)
4828 + m* 64 + 13 (channel 1, low byte) 4828 + m* 64 + 14 (channel 1, high
byte)
4828 + m* 64 + 15 (channel 2, low byte) 4828 + m* 64 + 16 (channel 2, high
byte)
4828 + m* 64 + 17 (channel 3, low byte) 4828 + m* 64 + 18 (channel 3, high
byte)
m = module number (0 ... 47)
Description
Setting of the lower critical limit for the individual channels of the analogue
input module è 7.6 Scaling the range of values.
– The lower critical limit must be smaller than the upper critical limit.
– The permissible values depend on the set data format è Tab. 18 Description
– With data format "linear scaling," the critical limits have the function of
Prerequisites for the monitoring of channel-specific parameterisation:
– The "Monitoring of parameterisation errors" module parameter is active
– The "Monitoring of parameterisation errors" channel parameter is active
Active monitoring has the following effect:
– Invalid values are not assumed. The last valid value is retained.
Festo — CPX-4AE-4AA-H — 2021-06b
– 0 = inactive (default)
– 1 = active
– 0 = inactive
– 1 = active (default)
of the "Data format, monitoring according to NAMUR NE43" module param-
eter.
scaling end values.
è Further information.
è Tab. 19 Description of "Monitoring of channel 0 ... 3".