Festo CPX-4AE-4AA-H Operating Instructions Manual page 29

Input module
Hide thumbs Also See for CPX-4AE-4AA-H:
Table of Contents

Advertisement

Commissioning
Module parameter: data format, monitoring according to NAMUR NE43
Function number
4828 + m* 64 + 6
m = module number (0 ... 47)
Description
Setting of the data format
Activation of monitoring according to NAMUR NE43:
– Monitoring effective for signal range 4 ... 20 mA (with and without HART)
– Error message if the input value undershoots or exceeds the critical limits
– Bit 0: data format setting
Allocation
– Bit 1 ... 3: reserved
– Bit 4: monitoring according to NAMUR NE43
– Bit 7: reserved
– Bit 0:
Values
– Bit 4:
Tab. 18: Description of the "Data format, monitoring according to NAMUR NE43" module parameter
Channel parameter: monitoring of channel 0 ... 3
Function number
4828 + m* 64 + 7
4828 + m* 64 + 8
4828 + m* 64 + 9
4828 + m* 64 + 10
m = module number (0 ... 47)
Festo — CPX-4AE-4AA-H — 2021-06b
according to NAMUR NE43
– 0 = Sign + 15 bit (default)
– 1 = linear scaling
– 0 = inactive (default)
– 1 = active