Terminal compartment X10

5.6.1

Cable entries

5.6.2

Supply voltage terminal assignment

Technical data subject to change without notice.
08/2019
- for Zone 2 / 22
When connecting cables and leads to supplies / communications equipment in increased
safety protected areas, Ex certified cable entries must be used which are suitable for each
type of cable and lead. You must maintain the protection concept "e" and include a suitable
sealing element so that an IP rating of at least IP 54 is maintained.
The terminal area of the M20 cable glands is printed on the cable glands.
A different terminal area may only be substituted with a cable gland that complies with
the current version of the approval.
The assembly instructions and installation conditions for the cable glands must be
observed.
Tightening torque of the cable glands
Torque
non-armoured cables
armoured cables
DANGER
If the power supply is active there is a danger of life in an explosive atmosphere!
Disconnect the device before starting work.
Only use certified cable glands that have been approved for the cable diameter of
the connection cable.
Unused cable glands must be sealed using an approved blanking plug.
Mains Connection Variant AC
Terminal Interface
X10
Supply
X11
Supply
X12
Supply
Mains Connection Variant DC 24 V
Terminal Interface
X10
Supply
X11
Supply
X12
Supply
Connecting thread
2.3 Nm
8 Nm
Signal
Remarks
L
AC 110 - 230 V ± 10 %
N
Neutral
PE
Protective earth
Signal
Remarks
+
DC 24 V ± 10 %
-
0 Volt
PE
Protective earth
Installation
Nut
1.5 Nm
5 Nm