Bartec POLARIS PROFESSIONAL B7-72V1 Series User Manual

Bartec POLARIS PROFESSIONAL B7-72V1 Series User Manual

Hide thumbs Also See for POLARIS PROFESSIONAL B7-72V1 Series:
Table of Contents

Advertisement

Quick Links

User Manual - TRANSLATION
POLARIS PROFESSIONAL
POLARIS Panel PC Professional 15" up to 24"
Type B7-72V1-....
ATEX
Zone 2 / 22
Document no. B1-72V1-7D0003
Status: 23 October 2019
Reservation: Technical data subject to change without notice. Changes, errors and
misprints may not be used as a basis for any claim for damages.
GmbH
Max-Eyth-Straße 16
97980 Bad Mergentheim
Germany
Contents
Page
English
1-66
Appendix
Declaration of Conformity
Phone:
+49 7931 597-0
Fax:
+49 7931 597-119
Contact:
support-polaris@bartec.de
Download:
www.bartec.de/automation-download
/

Advertisement

Table of Contents
loading

Summary of Contents for Bartec POLARIS PROFESSIONAL B7-72V1 Series

  • Page 1 Contents Page English 1-66 Appendix Declaration of Conformity GmbH Contact: Max-Eyth-Straße 16 Phone: +49 7931 597-0 support-polaris@bartec.de 97980 Bad Mergentheim Fax: +49 7931 597-119 Download: Germany www.bartec.de/automation-download...
  • Page 2 POLARIS PROFESSIONAL - for Zone 2 / 22 Table of Contents POLARIS Panel PC Professional 15" up to 24" Technical data subject to change without notice. 08/2019...
  • Page 3: Table Of Contents

    POLARIS PROFESSIONAL - for Zone 2 / 22 Table of Contents POLARIS Panel PC Professional 15" up to 24" Basic Safety Instructions........................1 Notes on this manual ........................ 1 1.1.1 Languages ........................2 1.1.2 Changes to the document .................... 2 Handling the Product.........................
  • Page 4 5.6.3 Ethernet terminal assignment ..................32 5.6.4 RS422 interface ......................32 5.6.5 RS485 interface ......................33 5.6.6 BARTEC PROFIBUS-DP Interface (optional)............. 34 5.6.7 TTY interface (optional) ....................35 5.6.8 RS232 interface (optional) ..................36 5.6.9 Siemens PROFIBUS-DP interface (optional) ............. 37 5.6.10 USB interface (onto terminals optional) ..............
  • Page 5 POLARIS PROFESSIONAL - for Zone 2 / 22 Table of Contents POLARIS Panel PC Professional 15" up to 24" Dispatch and Packaging Instructions ..................... 60 Accessories, Spare Parts ......................... 61 Order Numbers ..........................62 Additional Information ........................63 Appendix - Declaration of Conformity Technical data subject to change without notice..
  • Page 6 - blank -...
  • Page 7: Basic Safety Instructions

    POLARIS PROFESSIONAL - for Zone 2 / 22 Basic POLARIS Panel PC Professional 15" up to 24" Safety Instructions Basic Safety Instructions Notes on this manual Please read carefully before commissioning the devices. The user manual is a constituent part of the product. It must be kept in the direct vicinity of the device and accessible at all times to installation, operating and maintenance personnel.
  • Page 8: Languages

    In case of doubt, the German safety instructions shall apply because it is not possible to rule out errors in translation or in printing. In the event of a legal dispute, the “General Terms and Conditions” of the BARTEC group shall apply in addition.
  • Page 9: Owner's/Managing Operator's Obligations

    POLARIS PROFESSIONAL - for Zone 2 / 22 Basic POLARIS Panel PC Professional 15" up to 24" Safety Instructions Owner’s/Managing Operator’s Obligations The owner/managing operator undertakes to restrict permission to work with the POLARIS to people who: are familiar with the basic regulations on safety and accident prevention and have ...
  • Page 10: Inspection

    Basic POLARIS PROFESSIONAL - for Zone 2 / 22 Safety Instructions POLARIS Panel PC Professional 15" up to 24" 1.6.3 Inspection Under EN 60079-17, EN 60079-19, IEC 60079-17 and IEC 60079-19, the owner/ managing operator of electrical installations in hazardous areas is obliged to have these installations checked by a qualified electrician to ensure that they are in a proper condition.
  • Page 11 POLARIS PROFESSIONAL - for Zone 2 / 22 Basic POLARIS Panel PC Professional 15" up to 24" Safety Instructions As a fundamental rule, our “General Conditions of Sale and Delivery” apply. These are made available to the owner/managing operator at the latest on formation of a contract. Guarantee and liability claims for personal injury and damage to property are excluded if they are due to one or more of the following reasons: use of the POLARIS for a purpose other than that for which it is intended.
  • Page 12: Product Description

    The pre-installed, multi-lingual Windows® 7 Ultimate operating system (optional Windows® 10 IoT LTSB) allows the use of its standard visualisation or the BMS- Graf-pro 7 visualisation software from BARTEC. Illustration 2: Visualization software BMS-Graf-pro Version 7 Technical data subject to change without notice..
  • Page 13 The use of the power-limited USB interface (max. 100 mA), socket type A allows data to be transferred easily, stored, and saved for system restoration by means of a BARTEC recovery stick. (Do not insert the memory stick in an explosive atmosphere, see chapter “Power-limited USB interface for memory stick”...
  • Page 14: Schematic Diagram

    POLARIS PROFESSIONAL - for Zone 2 / 22 Product Description POLARIS Panel PC Professional 15" up to 24" Schematic diagram Ethernet RS422/ 232 /... Illustration 5: System configuration with Touch operation Ethernet e.g. RS422/ 232 /... Caps Scr o l l F11 F12 Dr uck Rol l e n Pause Lock Lock Lock...
  • Page 15: Technical Data

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" Technical Data POLARIS Panel PC Professional 3.1.1 Explosion Protection Type B7-72V1-..Ex protection type ATEX II 3G Ex nA IIC T4 Gc resp. II 3D Ex tc IIIC T120 °C Dc Standards EN 60079-0:2012 +A11:2013...
  • Page 16: General Data

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.1.2 General data Construction Front panel fitting; Optional turn-key system solutions in a stainless steel enclosure as wall, floor or ceiling mounting versions. Computer capacity Intel®...
  • Page 17: Characteristics Polaris Panel Pc 15" Professional

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.1.3 Characteristics POLARIS Panel PC 15" Professional Display 15" graphics-capable TFT display XGA resolution 1024 x 768 pixels - 16.7 million colours Brightness 350 cd/m Visible surface approx.
  • Page 18: Characteristics Polaris Panel Pc Professional 17.3

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.1.5 Characteristics POLARIS Panel PC Professional 17.3" Display 17.3" graphics-capable TFT display Full HD resolution 1920 x 1080 pixels 16.7 million colours Brightness 400 cd/m Visible surface approx.
  • Page 19: Characteristics Polaris Panel Pc Professional 24

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.1.7 Characteristics POLARIS Panel PC Professional 24" Display 24" graphics-capable TFT display Full HD resolution 1920 x 1080 pixels 16.7 million colours Brightness 300 cd/m Visible surface approx.
  • Page 20: Keyboard

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" Keyboard 3.2.1 Explosion Protection Type B7-72VZ-40.. Ex protection type ATEX II 3G Ex nA IIC T4 Gc II 3D Ex tc IIIC T120°C Dc Standards EN 60079-0:2012 + A11:2013 EN 60079-15:2010...
  • Page 21: Characteristics Enclosure For Mouse And Keyboard

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.2.3 Characteristics Enclosure for mouse and keyboard Order no. 05-0041-0277 Material Stainless steel 1.4301; AISI 304 Dimensions (width x height x depth) 600 mm x 85 mm x 220 mm Protection class IP65...
  • Page 22: General Data

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.3.2 General Data Construction Front panel fitting Material Polyester foil on aluminium sheet (conditionally UV-resistant) Protection class Mouse, Joystick, Touchpad IP65 (front side) Trackball static IP65 (front side)
  • Page 23: Usb Smart Device

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" USB Smart Device 3.4.1 Explosion protection Type 17-71VZ-A0x0/0000 Ex protection type ATEX II 2G Ex eb mb IIC T4 Gb II 2D Ex tb IIIC T120 °C Db Certification IBExU 05 ATEX 1117 X Kennzeichnung IECEx...
  • Page 24: Electric Data (Usb Standard)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" 3.4.3 Electric data (USB standard) USB-connection Colour Function Data- USB-data signal Data+ USB-data signal Bluetooth 3.4.4 Technical data (Bluetooth) Bluetooth Downward compatible 2.0/2.1/3.0 Range Up to 10m (open terrain)
  • Page 25: Product Labelling

    POLARIS PROFESSIONAL - for Zone 2 / 22 Technical Data POLARIS Panel PC Professional 15" up to 24" Product Labelling Example: Type label with label ATEX Warnings on the device Licence sticker Test sticker Technical data subject to change without notice. 19/66 08/2019...
  • Page 26: Transport And Assembly

    A written report of any transport damage or missing items must be given to the appointed forwarder and to BARTEC GmbH immediately on receipt of the delivery. Damage caused by incorrect storage and transport shall not fall within the warranty provisions of BARTEC GmbH.
  • Page 27: Assembly

    POLARIS PROFESSIONAL - for Zone 2 / 22 Transport and Assembly POLARIS Panel PC Professional 15" up to 24" Assembly Before assembling the device, make sure you have all the components and documents. Required POLARIS 1 x hex key 3 mm (mounting clamps) 1 x slotted screwdriver Tools:...
  • Page 28: Installation

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Installation We recommend setting up and testing the entire system before its ultimate installation in the ex-area. If a long connection cable is not available, please use a patch cable to test the basic functions.
  • Page 29: Mechanical Installation

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Choose the optimum height for operating the POLARIS. – Ensure good lighting conditions for a perfectly legible display – (no direct exposure to the sun’s rays). Do not mount in direct proximity to switching or current changing devices.
  • Page 30: Installation In 3G-/3D Enclosure

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.2.1 Installation in 3G-/3D enclosure In order to guarantee the IP degree of enclosure protection = IP54 for installation in 3G enclosures of Ex e type of protection (e.g. control equipment), and = IP6X for installation in 3D enclosures in areas where combustible dusts exist - with “protection through the enclosure”...
  • Page 31: Installation As A System Solution In The Stainless Steel Enclosure

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Work steps Insert the POLARIS into the cut-out in the enclosure. From the back, place the reinforcement frame over the POLARIS. Using the M4x12 (2) screws to fasten the mounting clamps (1) to the rear side of the POLARIS and tighten to 1.37 Nm.
  • Page 32 POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Work steps (Stainless steel enclosure "Exclusive II") Prepare supply and data line(s). Prepare installation on the basis of the drilling template (see illustration 6 - 8). Install supply and data line(s) in the base.
  • Page 33 POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.2.3 Table mounting swivel/tilt (Stainless steel enclosure "Exclusive II") CAUTION Movable enclosure parts on the swivel-mounted enclosure. There is a risk of injury by hands being crushed. 3 people are needed for assembly/disassembly.
  • Page 34: Electrical Installation

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Electrical Installation 5.3.1 Installation guidelines Only qualified personnel, i.e. trained electricians will have the required specialised knowledge to be able to do all the electrical work. Familiarity with and the technically perfect implementation of the safety instructions described in this manual are preconditions for safe installation and commissioning.
  • Page 35: Terminal Compartments

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Terminal compartments DANGER Sealed locking screw! The device is closed in the factory. The explosion protection is lost if opened, and danger to life exists in an explosive atmosphere! Do not open the locking screw! ...
  • Page 36: Pe Conductor Connection

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" PE conductor connection DANGER Death or danger of injury as a result of no PE conductor connection. There is no explosion protection. Equipotential bonding with a core cross-section of at least 4 mm is to be set up ...
  • Page 37: Terminal Compartment X10

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Terminal compartment X10 5.6.1 Cable entries When connecting cables and leads to supplies / communications equipment in increased safety protected areas, Ex certified cable entries must be used which are suitable for each type of cable and lead.
  • Page 38: Ethernet Terminal Assignment

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.6.3 Ethernet terminal assignment Configuration Ethernet Terminal Interface Signal Remarks Ethernet RxD + 10BaseT Receive positive Ethernet RxD - 10BaseT Receive negative Ethernet TxD + 10BaseT Transmit positive...
  • Page 39: Rs485 Interface

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Setting of the terminal resistors at the start and end of the bus line is not necessary in most cases due to internal EMC measures. Depending on local circumstances, the data transmission may worsen in individual cases.
  • Page 40: Bartec Profibus-Dp Interface (Optional)

    - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.6.6 BARTEC PROFIBUS-DP Interface (optional) The interface PROFIBUS-DP (BARTEC) may only be applied in combination with visualization software BMS-Graf-pro 7. Configuration PROFIBUS-DP (BARTEC) Terminal Interface Signal...
  • Page 41: Tty Interface (Optional)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.6.7 TTY interface (optional) Configuration TTY Terminal Interface Signal Remarks Not connected Not connected Interface COM 1 Signal ground for receiver Interface COM 1 Cathode Interface COM 1 Anode...
  • Page 42: Rs232 Interface (Optional)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.6.8 RS232 interface (optional) Configuration RS232 Terminal Interface Signal Remarks Not connected Not connected Not connected Not connected Not connected Not connected Not connected Interface COM 1 Receive Interface COM 1...
  • Page 43: Siemens Profibus-Dp Interface (Optional)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.6.9 Siemens PROFIBUS-DP interface (optional) Configuration Siemens PROFIBUS (supported only WinCC flexible) Terminal Interface Signal Remarks Not connected Not connected Interface COM 1 Termination Interface COM 1 Termination...
  • Page 44: Usb Interface (Onto Terminals Optional)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.6.10 USB interface (onto terminals optional) Configuration USB Terminal Interface Signal X17 - X22 not connected +5 V Data- USB data signal Data+ USB data signal The individual conductors are colour-coded in a 4-wire USB cable as follows: Panel PC...
  • Page 45: Terminal Compartment X1

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Terminal compartment X1 5.7.1 Cable entries When connecting cables and leads to supplies / communications equipment in the Ex area, Ex certified cable entries must be used which are suitable for the respective type of cable and lead.
  • Page 46: Power-Limited Usb Interface For Memory Stick

    USB socket, 4-pole, Type A The power-limited USB interface (max. 100 mA), socket type A allows data to be transferred easily, stored, and saved for system restoration by means of a BARTEC recovery stick. DANGER Do not insert the memory stick in an explosive atmosphere.
  • Page 47: Fibre-Optic Port (Optional)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.7.4 Fibre-optic port (optional) For the fibre-optic transmission a fibre-optic converter is used inside the POLARIS and it converts the Ethernet/IP to fibre-optic signals (Ethernet/IP Ex e connection is not required). For transmission a converter of the same type is needed for the non-hazardous area.
  • Page 48: Emc (Electromagnetic Compatibility)

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" EMC (Electromagnetic Compatibility) This is a class A unit and can cause radio interference in residential areas; if it does, the owner/managing operator may be required to implement suitable measures and pay for loss or damage.
  • Page 49: Back-Up Fuse

    Eska 2 A M 1000A@250VAC We recommend protecting the POLARIS with an upstream fuse to prevent blowing the fuse inside the device. Only BARTEC can change the internal fuse. Upstream fuse for AC: 1.6 A quick-acting (since June 2015: 2.5 A) DC: 4 A quick-acting.
  • Page 50: Shielding

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" 5.8.4 Shielding - Only cables with braided shielding should be used (recommended cover density > 80 %). - Sheet shielding should not be used. - Generally, connection of the shielding at both ends results in optimum damping of all interference frequencies.
  • Page 51: Ethernet

    POLARIS PROFESSIONAL - for Zone 2 / 22 Installation POLARIS Panel PC Professional 15" up to 24" Connection of the shielding at one end only is recommended when there is inadequate equipotential bonding, or none at all. In such cases an electrically isolated power supply unit must be used.
  • Page 52: Commissioning

    POLARIS PROFESSIONAL - for Zone 2 / 22 Commissioning POLARIS Panel PC Professional 15" up to 24" Commissioning For electrical systems the relevant installation and operating specifications (e.g. Directives 99/92/EC and 94/9/EC, BetrSichV and the applicable national ordinances, EN 60079-14, IEC 60079-14 and the DIN VDE 0100 series) must be observed.
  • Page 53: Operation

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" Operation Once the final inspection has been carried out, the device can be put into operation. The POLARIS series does not have any ON/OFF switch. Operating System The POLARIS series devices have the Windows 7 Ultimate or the Windows 10 IOT Enterprise LTSB operating system pre-installed.
  • Page 54: Commissioning Software

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" Commissioning Software 7.2.1 Windows 10 Iot Enterprise LTSB The devices are delivered with active writing filter (UWF). This UWF prevents that changes in the disk drive C: can be made. To carry out changes the UWF must be deactivated.
  • Page 55: On-Board Bartec Recovery Solution

    The Bartec HMI Polaris Smart devices are equipped with an On-Board-Recovery solution. The Bartec Recovery is a software package preloaded on the devices which serves the disregard of the device in the work state. In case of a mistake every device can be booted up in the Recovery mode to move afterwards the operating system into the work state.
  • Page 56: Recovery Application

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" As soon as the surroundings are completely loaded and are ready for use, the Recovery engine will check in the background whether the applications necessary for the device, tools and drivers exist.
  • Page 57: Restoration In The Work State

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" To accept the licence terms, the option "I accept the terms in the End User License Agreement" must be activated or be selected. The button "Start Recovery" is released enclosed.
  • Page 58 POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" In the upper area of the window the inscription of the well-chosen function is indicated. In the next line – the inscription of the already running background process. Should a process be computable, the proportional issue appears in the next line how far the process is already concluded.
  • Page 59: Finish The Recovery

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" Illustration 23: Prepare the partition After preparing the partition all files from the effigy image stored on the Recovery partition are unpacked and transferred on the operating system partition. Illustration 24: Transferred by system files on operating system partition Transferring of system files is the last process with the Recovery of the operating system in...
  • Page 60: Recovery/Backup Function

    Recovery/Backup Function The POLARIS can be restored to delivery status by means of a BARTEC recovery stick. The BARTEC recovery stick is not included in the scope of supply. It can be ordered from the contact address support-polaris@bartec.de...
  • Page 61: Backup

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" 7.4.2 Backup We expressly point out that it is the user’s responsibility to make a backup of the POLARIS and all its functions! We expressly recommend that such a backup of the POLARIS be saved on an external storage medium (USB stick [recovery stick], CD, DVD or suchlike) and/or in the company network!
  • Page 62: Network (Ethernet) Setup With Windows Xp

    POLARIS PROFESSIONAL - for Zone 2 / 22 Operation POLARIS Panel PC Professional 15" up to 24" Network (Ethernet) setup with Windows XP 7.5.1 Requirements Network (Ethernet) setup: Physical connection (connection of Ethernet cable to a network (e. g. switch, hub, server) Go to Start ...
  • Page 63: Touch Screen

    HUB). Figure 3 Figure 4 Touch Screen In the device variants with touchscreen, the touchscreen software is pre-installed already. The touch screen software is available for download at: http://www.bartec.de/automation-download/ Technical data subject to change without notice. 57/66 08/2019...
  • Page 64: Faults And Troubleshooting

    POLARIS PROFESSIONAL Faults and troubleshooting POLARIS Panel PC Professional Faults and Troubleshooting Fault Possible cause Remedy No power supply present Check connection of the power supply External back-up fuse has Check fuse tripped Internal fuse has tripped Return to the manufacturer Nothing is shown on the display Return to the manufacturer...
  • Page 65: Maintenance, Inspection, Repair

    POLARIS PROFESSIONAL - for Zone 2 / 22 Repair, Disposal, POLARIS Panel PC Professional 15" up to 24" Dispatch and Packaging Maintenance, Inspection, Repair Only trained and qualified personnel may commission and do maintenance work on the POLARIS! Trained qualified personnel are people who are familiar with the installation, assembly, commissioning and operation of the POLARIS, have been instructed about the risks and have the appropriate qualifications by virtue of the work they do.
  • Page 66: Instructions For Repairs

    Then fill in and sign the RMA (Return Merchandise Authorisation) form and send it to our "Retouren Center". E-mail: services@bartec.de Fax: +49 7931 597-119 We cannot guarantee any contractually agreed processing times for devices that are sent in without an RMA number.
  • Page 67: Accessories, Spare Parts

    1.8 m 03-0068-0183 3.0 m 03-0068-0206 USB Device WLAN (Ex d socket necessary) 17-71VZ-6000/0100 BARTEC Recovery stick on request Enclosure "Exclusive" POLARIS Panel PC 15" 03-8900-0224 POLARIS Panel PC 19.1" 03-8900-0225 POLARIS Panel PC 24" on request...
  • Page 68: Order Numbers

    POLARIS PROFESSIONAL - for Zone 2 / 22 Order Numbers POLARIS Panel PC Professional 15" up to 24" Order Numbers POLARIS Panel PC 15" / Panel PC 19.1" / Panel PC 24" POLARIS Panel PC 15" Sunlight Technical data subject to change without notice.. 62/66 08/2019...
  • Page 69: Additional Information

    POLARIS PROFESSIONAL - for Zone 2 / 22 Additional Information POLARIS Panel PC Professional 15" up to 24" Additional Information Technical data subject to change without notice. 63/66 08/2019...
  • Page 70 POLARIS PROFESSIONAL - for Zone 2 / 22 Appendix POLARIS Panel PC Professional 15" up to 24" Declaration of Conformity POLARIS Panel PC All certificates see www.bartec-group.com  Technical data subject to change without notice 64/66 08/2019...
  • Page 71 POLARIS PROFESSIONAL - for Zone 2 / 22 Appendix POLARIS Panel PC Professional 15" up to 24" User Notes Technical data subject to change without notice. 65/66 08/2019...
  • Page 72 POLARIS PROFESSIONAL - for Zone 2 / 22 Appendix POLARIS Panel PC Professional 15" up to 24" User Notes Technical data subject to change without notice 66/66 08/2019...
  • Page 73 POLARIS PROFESSIONAL - for Zone 2 / 22 Appendix POLARIS Panel PC Professional 15" up to 24" User Notes Technical data subject to change without notice. 67/66 08/2019...

Table of Contents