Table 4.3: ADAM-4017+ Command Table
Command Syntax Command Name
%AANNTTCCFF
Configuration
$AA2
Configuration Status
Read Firmware
$AAF
Version
$AAM
Read Module Name
Read Analog Input
#AA
from all Channels
Read Analog Input
#AAN
from Channel N
Enable/Disable
$AA5VV
Channels for Multi-
plexing
$AA6
Read Channel Status
Single Channel
$AA0Ci
Span Calibration
Single Channel
$AA1Ci
Offset Calibration
Single Channel
$AA7CiRrr
Range Configuration
Read Single Chan-
$AA8Ci
nel Range Configura-
tion
Watchdog Timer
$AAXnnnn
Setting
Read Watchdog
$AAY
Timer Setting
Command Description
Sets the address, input range, baud
rate, data format, checksum status,
and/or integration time for a specified
analog input module
Return the configuration parameters
for the specified analog input module
Return the firmware version code
from the specified analog input mod-
ule
Return the module name from the
specified analog input module
Return the input values from all chan-
nels of the specified analog input
module
Return the input value from channels
number N of the specified analog
input module
Enable or disable the individual chan-
nels in an analog module
Get the enable/disable status of all
channels in an analog module
Calibrates a specified channel to cor-
rect for gain errors
Calibrates a specified channel to cor-
rect for offset errors
Configure the input type and range of
the specified channel in an analog
input module
Get the input type and range of the
specified channel in an analog input
module
Set communication WDT cycle time
from 0000 ~ 9999 (unit: 0.1 second. if
value is 0000, the communication
WDT function will be disable)
Read the cycle time setting of com-
munication WDT
71
ADAM-4000 Series User Manual
Page No.
5-4
5-10
5-12
5-13
5-14
5-16
5-17
5-18
5-27
5-28
5-29
5-30
5-31
5-32

Hide quick links: