4015, 4017+, 4018+, 4019+
5.1.19

$AA8Ci

Name
Description This command read the input type and range configuration
Syntax
Response
Example
Read Single Channel Range Configuration command
of the specified channel in an analog input module.
$AA8Ci(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be read.
8 is the Read Single Channel Range Configuration command.
Ci represents the specified input channel you want to read.
(cr) is the terminating character, carriage return (0Dh).
!AACiRrr(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
Ci represents the specified input channel you read.
Rrr represents the type and range setting in the specified channel.
(Refer to Table 5-1 on Page 5-6 to check range codes)
(cr) represents terminating character, carriage return (0Dh).
command: $028C5(cr)
response: !02C5R21(cr)
The command read the range of channel 5 in the analog
input module at address 02. The response "R21" means
Pt100 (IEC) 0 ~ 100 °C.