Advantech ADAM 4000 Series User Manual page 170

Data acquisition modules
Hide thumbs Also See for ADAM 4000 Series:
Table of Contents

Advertisement

4080
7.2.1.3
$AAF
Name
Description The command requests the analog input module at address
Syntax
Response
4080
7.2.1.4
$AAM
Name
Description The command requests the counter/frequency module at
Syntax
Response
ADAM-4000 Series User Manual
Read Version command
AA to return the version code of its firmware.
$AAF (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
F is the Read Version command.
(cr) is the terminating character, carriage return (0Dh).
!AA(Version)(cr) if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! is a delimiter character which indicates a valid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(Version) is the version code of the module's firmware at address AA.
(cr) is the terminating character, carriage return (0Dh).
Read Module Name command
address AA to return its name
$AAM (cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
M is the Read Module Name command.
(cr) is the terminating character, carriage return (0Dh).
!AA(Module Name)(cr) if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! is a delimiter character which indicates a valid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(Module Name) is the name of the module at address AA.
For example, 4080D
(cr) is the terminating character, carriage return (0Dh).
158