Aa8 - Advantech ADAM 4000 Series User Manual

Data acquisition modules
Hide thumbs Also See for ADAM 4000 Series:
Table of Contents

Advertisement

4021
6.1.8

$AA8

Name
Description The addressed analog output module is instructed to
Syntax
Response
Example
Current Readback command
measure the current flowing through its current/voltage
loop and return the measured data in the module's
configured data format. The value returned may be a rough
estimate of the real value.
$AA8(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog output module that you want to
retrieve the data from. The data are current/voltage loop.
8 is the Current feedback command.
(cr) is the terminating character, carriage return (0Dh).
!AA(data)(cr) if the command was valid.
?AA(cr) if an invalid command was issued.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! delimiter character indicates that a valid command was received.
? delimiter character indicates that the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog output module.
(data) is the value returned by the analog output module.
(cr) is the terminating character, carriage return (0Dh).
command: $0A8(cr)
response: !0A18.773(cr)
The command tells the analog output module at address
0Ah to measure its current loop and return the measured value.
The analog output module returns the value 18.773 mA.
125
ADAM-4000 Series User Manual

Hide quick links:

Advertisement

Table of Contents
loading