4080
7.2.3.4
$AA0H
Name
Description Read the minimum input signal width at high level for a
Syntax
Response
Example
ADAM-4000 Series User Manual
Read Minimum Input Signal Width at High Level command
specified counter/frequency module.
$AA0H(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
0H is the Read Minimum Input Signal Width at High Level command.
(cr) is the terminating character, carriage return (0Dh).
!AA(data)(cr) if the command is valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! is a delimiter character which indicates a valid command.
? is a delimiter character which indicates an invalid command.
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
(data) is the minimum width at high level. The unit is in
μsec (microseconds) and its resolution is 1 μsec. The
format is a five digit integer that ranges from 2 μsec to
65535 μsec.
(cr) is the terminating character, carriage return (0Dh).
command: $130H(cr)
response: !1300020(cr)
The command requests the counter/frequency module at
address 13 to read its minimum input signal width at high
level. The module replies that its minimum input signal
width at high level is 20 μsec.
174