4080
7.2.2.8
$AA7N
Name
Description The command requests the module to return the status of
Syntax
Response
Example
ADAM-4000 Series User Manual
Read/Clear Overflow Flag command
the overflow flag for either counter 0 or counter 1. Then
clear the flag afterwards.
$AA7N(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address that you will access to.
7 is the Read/Clear Overflow Flag command.
N determines the channel whose overflow flag status
should be read and cleared. When N = 0, it represents
counter 0. On the other hand, N = 1 represents counter 1
(cr) is the terminating character, carriage return (0Dh).
!AAV(cr) if the command is valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
! is a delimiter character which indicates a valid command.
? is a delimiter character which indicates an invalid command .
AA (range 00-FF) represents the 2-character hexadecimal
address of the module.
V represents the status of the Nth channel's overflow flag.
V = 1 means that the overflow flag has been set because the
counting has exceeded the maximum count.
V = 0 means that the overflow flag has not been set.
(cr) is the terminating character, carriage return (0Dh).
command: $1371(cr)
response: !131(cr)
The command requests the counter/frequency module at
address 13 to return the status of the overflow flag for
counter 1 and to reset it. The module replies with the
overflow flag for counter 1indicating overflow. Then it is being reset.